1) Bypass setting
Interface
2) ECO setting (only available or effective on bypass mode)
Interface
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14
All manuals and user guides at all-guides.com
Description
1. Status (only available in bypass / AC mode)
1.1 Open/Forbid:
Open: Bypass allowed. When selected, UPS will run at Bypass mode depending on
bypass enabled/disabled setting.
Forbid: Bypass not allowed. When selected, it's not allowed for running in Bypass
mode under any situations.
1.2 Enable/Disable
This option appears only when Bypass status is set to "Open".
Enable: Bypass enabled. When selected, Bypass mode is activated.
Disable: Bypass disabled. When selected, automatic bypass is acceptable, but
"manual bypass" is not available. "Manual bypass" means users manually operate
UPS to Bypass mode (for example, in AC mode turning off the UPS to Bypass mode).
Then, the UPS will go to
mode.
NOTE: The following items are only available in bypass mode:
2. HighLoss V: Set the acceptable high voltage for bypass. Setting range is from (Rated
Output Volt +11V) to 276V and the default value is 264V.
3. LowLoss V: Set the acceptable low voltage for bypass. Setting range is from 110V to
(Rated Output Volt - 11V) and the default value is 110V.
4. HighLoss F: Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51Hz to 54 Hz.
60 Hz: Setting range is from 61Hz to 64Hz.
The default value is 54.0Hz/64.0Hz.
5. LowLoss F: Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46Hz/56Hz.
Description
1. Status
Enable: Enable ECO Function
Disable: Disable ECO Function
If ECO function is disabled, voltage range and frequency range for ECO mode still can
be set, but it is meaningless unless the ECO function is enabled.
2.
HighLoss V: High voltage point in ECO mode. The setting range
is from +5% to +10% of the nominal voltage.
3.
LowLoss V: Low voltage point in ECO mode. The setting range is
from -5% to -10% of the nominal voltage.
4. HighLoss F: Set low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
5.
LowLoss F: Set high frequency point for ECO mode.
50 Hz: Setting range is from 52.0Hz to 54.0 Hz.
60 Hz: Setting range is from 62.0Hz to 64.0Hz.
The default value is 52.0Hz/62.0Hz.
bypass mode but without output
if it is turned off in AC
21