2.3 Setup the UPS
Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the following
instructions by professional personnel.
1)
Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the
hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS's
maximum input current. Otherwise the receptacle may be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the connected devices before connecting to the UPS.
4)
Prepare wires based on the following table:
Model
5KRT(S)
6KRT(S)
8KRT(S)
10KRT(S)
NOTE 1: The cable for 5KRT(S) and 6KRT(S) should be able to withstand over 40A current. It is recommended to
use 10AWG/6mm² or thicker wire for safety and efficiency.
NOTE 2: The cable for 8KRT(S) and 10KRT(S) should be able to withstand over 63A current. It is recommended to
use 8AWG/10mm² or thicker wire for safety and efficiency.
NOTE 3: The selections for color of wires should be followed by the local electrical laws and regulations.
NOTE 4: External battery wires must use reinforced insulation or double insulated wire.
5)
Remove the terminal block cover on the rear panel of UPS, Then connect the other wires according to the following
terminal block diagrams:
6)
Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire
disconnection!
10
All manuals and user guides at all-guides.com
Wiring spec (AWG/mm²)
Input
Output
8 / 6
8 / 6
8 / 6
8 / 6
6 / 10
6 / 10
6 / 10
6 / 10
Terminal Block wiring diagram of UPS
Terminal Block wiring diagram of 5K S /6K S & 8K S /10K S ISO BANK
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 05 13 AA 59 206 14
Battery
Ground
8 / 6
10 / 6
8 / 6
10 / 6
8 / 6
6 / 10
8 / 6
6 / 10