Haier HFU-09HA03(B)/R1 Manual De Funcionamiento página 32

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

All manuals and user guides at all-guides.com
Installation Manual of Room Air Conditioner
Note: When additional refrigerant is necessary, first purge air out of connecting pipe by external gas,
then drive out the excessive refrigerant by purging method..
Brand new unit is charged 80g more refrigerant than spec. This is only for first installation to purge air
in the indoor unit and connecting pipe.
When piping is longer than 5m, change additional refrigerant specified in this list.
Pipe length
Refrigerant charge(g)
Electric wiring
Note:
Electric wiring must be done by qualified person.
Use copper wire only.
The parameter of the connecting cable is H05RN-F or H07RN-F
2
3G1.5mm
+1x0.75mm
Wiring of indoor unit
Insert the cable from outside the wall hole where piping already exist.
Pull it out from front.
Loose terminal screw and insert cable end fully into terminal block, then tighten it
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Terminal block
Wire clip
Wire loop
Wiring of outdoor unit
Insert the cable from inside the wall hole where piping already exist.
Pull it out from front.
Loose terminal screw and insert cable end fully into terminal block, then tighten it
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal
blocks. Terminals of same number and same color shall be connected by the same wire.
Incorrect wiring may damage air conditioner's control or cause operation failure.
5m
10m
90
2
White
Black
29
15m
180
Indoor unit
1(N)
2(L)
3(C)
N
L
Yellow/Green
Red
Outdoor unit
power

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Hfu-12ha03(b)/r1Hfu-09h03/r2(db)Hfu-12h03/r2(db)

Tabla de contenido