EDM Product 07688 Manual Del Usuario página 33

Desumidificador de toque suave
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCCIONES IMPORTANTES DE SEGURIDAD
Ref. 07688
INSTRUÇÕES IMPORTANTES DE SEGURANÇA / IMPORTANT SAFETY INSTRUCTIONS
recovery machine, check that it is in satisfactory working order, has been properly maintained and that any
associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult
manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been
evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the
lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from
a system, it shall be carried out safely.
Fuse parameters of the machine
Type: 5H or 524 Voltage: 250V Current: 3.15 A

Publicidad

Tabla de contenido
loading

Tabla de contenido