Specifications
Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.9 °C)
Shipping Temperature
-20 °F to 120 °F (-28.9 °C to 48.9 °C)
Electrical Ratings
Terminal
W Heating
(Powerpile)
W2 (Aux) Heating
E Emergency Heat
Y Compressor Stage 1
Y2 Compressor Stage 2
G Fan
O/B Changeover
L/A Input
U
Power Consumption
Backlight On: 1.48VA
Backlight Off: 0.88VA
5-year limited warranty
For Warranty information go to
http://customer.resideo.com
Regulatory information
FCC REGULATIONS
47 CFR § 15.19 (a)(3)
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired
operation.
47 CFR § 15.21 (USA only)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user's
authority to operate the equipment.
47 CFR § 15.105 (b)
See https://customer.resideo.com/en-US/support/
residential/codes-and-standards/FCC15105/Pages/
default.aspx for additional FCC information for this
product.
Voltage
Running Current
(50Hz/60Hz)
20 Vac-30 Vac
0.02 A-1.0 A
750 mV DC
100 mA DC
20 Vac-30 Vac
0.02 A-1.0 A
20 Vac-30 Vac
0.02 A-0.5 A
20 Vac-30 Vac
0.02 A-1.0 A
20 Vac-30 Vac
0.02 A-1.0 A
20 Vac-30 Vac
0.02 A-0.5 A
20 Vac-30 Vac
0.02 A-0.5 A
20 Vac-30 Vac
0.02 A-0.5 A
20 Vac-30 Vac
0.02 A-0.5 A
21
Operating Relative Humidity
5% to 90% (non-condensing)
Physical Dimensions in inches (mm) (H x
W x D)
T6 Pro Smart Thermostat (TH6320WF2003):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
T6 Pro Smart Thermostat (TH6220WF2006):
4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
IC REGULATIONS
RSS-GEN
This device contains licence-exempt transmitter(s)/
receiver(s) that comply with Innovation, Science and
Economic Development Canada's licence-exempt RSS(s).
Operation is subject to the following two conditions:
1. This device may not cause interference.
2. This device must accept any interference, including
interference that may cause undesired operation of
the device.
The operation of this equipment is subject to the following
two conditions: (1) this equipment or device may not cause
harmful interference, and (2) this equipment or device must
accept any interference, including interference that may
cause undesired operation.