LEGRAND Wattstopper CI-300 Instrucciones De Instalación página 2

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Each Wattstopper BZ series power pack can supply power for 8 CI-300
sensors. When using more sensors than this, multiple power packs are
required.
Refer to the wiring diagram for the following procedures:
Connect the low voltage:
• RED wire (+24VDC) from power pack to the +24V terminal on the sensor.
• BLACK wire (Return) from power pack to Common terminal on the sensor.
• BLUE wire from power pack to Control Out terminal on sensor.
To add a manual switch such as the LVS-1 Momentary Toggle Switch, or
RS2-3 Low Voltage Momentary Switch to the above applications–connect:
• Wire from one side of switch to +24 terminal on sensor.
• Wire from other side of switch to Man Switch terminal on sensor.
Wiring the Isolated Relay: (The Isolated Relay is rated for 1A@30VAC/VDC)
Connect the wires necessary to the application that requires this output:
• Relay Common (must be used for proper operation).
• N.O. (Normally Open)–Closed when occupancy is detected.
• N.C. (Normally Closed)–Open when occupancy is detected.
Care should be taken to separate high voltage power from low voltage (Class 2) control wiring.
All connections to sensor are low voltage, Class 2.
Standard wiring with local off switch
Line
Neutral
Power Pack
Low Voltage
Class 2
Black
Common
Blue
Red
Control Out
+24V
Ceiling
Depluggable
Terminal
Spring Clips (2)
Rear Housing
Front Cover
CI-300
MOUNTING THE SENSOR DIRECTLY TO CEILING
1. Attach the plastic spring clips to the edge of the sensor in the slots provided.
2. Cut a 3.5" to 4" round hole in the acoustic ceiling tile at the mounting location.
A 3.5" hole is recommended for a secure fit.
3. Pull the low voltage wire from the power pack to the sensor through the hole.
4. Connect the low voltage wires to the appropriate terminals on the sensor.
5. Push the sensor up through the hole until the Spring Clips hold the sensor
securely in place.
6. Snap the front cover onto the sensor. Using an Octagonal J-Box
7. Pull the low voltage wires from the power pack into the J-Box through the conduit
knockout.
WIRING DIRECTIONS
Feed Through
Load #1
Load #2
(Optional)
Line
Voltage
Ceiling
Depluggable
Terminal
Spring Clips (2)
#1
#2
Rear Housing
Line Voltage
Switches
Front Cover
2
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
Manual-On wiring with low voltage momentary switch
Line
Neutral
Power Pack
Low Voltage
Class 2
Red
+24V
Blue
Black
Control Out
Common
Man.Switch
CI-300
CI-300
Relay Com.
v5
Passive Infrared
N.O.
Occupancy Sensor
+24VDC/VAC
N.C.
Connect to Watt Stopper
Class 2 Power Packs
For Indoor Use Only
Control Out.
Appliance
Control
88T9
Man. Switch
LISTED
E101196
+24V
Common
www.legrand.us/wattstopper
Wiring
terminals
Feed Through
Load
Line Voltage
+24V
Man.Switch
Jumper
Back
of
LVS-1
LVS-1
For low voltage
momentary switch set
DIP switches #7 ON
Ceiling Mount

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Wattstopper ci-300-1Ci-300Ci-300-1

Tabla de contenido