Descargar Imprimir esta página

LEGRAND DPX3 160 - 250 Guia De Inicio Rapido página 11

Ocultar thumbs Ver también para DPX3 160 - 250:

Publicidad

Caractéristiques techniques / Technical features / Caratteristiche tecniche / Características técnicas / Technische specificaties / Características técnicas /
Технические характеристики / Dane techniczne / Teknik özellikler
AC power: terminals 53, 54
Us rated voltage
Operating limits
Frequency
Drawn/dissipated power
Micro-interruption immunity time
(without expansion modules)
Micro-interruption immunity time
DC Power: terminals 26, 27
Rated battery voltage
Operating limits
Maximum drawn current
Maximum drawn/dissipated power
Recommended fuses
Voltmeter inputs Line 1, Line 2: terminals 1 to 4, 5 to 8
Ue max rated voltage
Measuring range
Frequency range
Measurement type
Measurement input impedance
Connection modes
Measurement accuracy
AC voltage inputs
Digital inputs: terminals 39 to 47
Input type
Input current
Low input signal
High input signal
Input signal delay
Digital inputs: terminals 15 - 20
Input type
Current input
Input "low" voltage
Input "high" voltage
Input delay
RS485 serial interface: terminals 22 to 25
Interface type
Baudrate
Real Time Clock
Reserve charge
Operation without power voltage
Outputs OUT1, OUT3: terminals 55-56, 58-59
Contact type
Rating
Maximum usage voltage
Electrical/mechanical time
Maximum current on terminals 55,
59 and 62
Outputs OUT2, OUT4: terminals 56-57, 59-60
Contact type
Rating
Maximum usage voltage
Electrical/mechanical time
Maximum current on terminals 55,
59 and 62
100 - 240V AC
90 - 264V AC
45 - 66Hz
100V AC 12.5VA; 7W
240V AC 16.5VA; 7,3W
≤ 40ms (110V AC)
≤ 200ms (220V AC )
≤ 20ms (110V AC)
≤ 100ms (220V AC)
F1A (fast)
12 - 48V DC
7.5 – 57.6V DC
510mA at 12V DC
260mA at 24V DC
135mA at 48V DC
6.5W
T3.15A (delayed)
600VAC L-L (346VAC L-N)
50 ÷ 720V L-L (415VAC L-N)
45 ÷ 65Hz – 360 ÷ 440Hz
True RMS (TRMS)
> 0.55MΩ L-N
> 1,10MΩ L-L
Three-phase line with or without neutral
balanced three-phase
±0,25% f.s. ±1digit
negative
≤8mA
≤2.2V
≥3.4V
≥50ms
Negative
≤8mA
≤2,2
≤3,4
≤50ms
Isolated
programmable 1200 ÷ 38400 bps
Back-up capacitor
Approximately 14 days
3 x 1 NO
AC1 - 12A 250V AC
AC15 -1.5A 250V AC
300V AC
10
7
/ 10
5
operations
12A
3 x 1 NO
AC1 - 8A 250V AC
AC15 -1,5A 250V AC
300V AC
10
/ 10
operations
7
5
12A
Outputs OUT7, OUT9, OUT10: terminals 19-21, 30-32, 33-35
Contact type
Rating
Maximum usage voltage
Electrical/mechanical time
Insulation voltage
AC power
Rated insulation voltage U
i
Rated impulse withstand voltage U
Operating frequency withstand
voltage
Voltmeter inputs Line 1, Line 2
Rated insulation voltage U
i
Rated impulse withstand voltage U
Operating frequency withstand
voltage
Output OUT1-2, OUT3-4
Rated insulation voltage U
i
Rated impulse withstand voltage U
Operating frequency withstand
voltage
Output OUT7, OUT9, OUT10
Rated insulation voltage U
i
Rated impulse withstand voltage U
Operating frequency withstand
voltage
RS485 serial interface
Rated impulse withstand voltage U
Operating frequency withstand
voltage
Ambient operating conditions
Temperature of use
Storage temperature
Relative humidity
Maximum environmental pollution
Overvoltage category
Measurement category
Climate sequence
Shock resistance
Vibration resistance
Connections
Terminal types
Wire cross-section area (min. and max.)
Tightening torque
Housing
Installation
Material
Frontal degree of protection
Weight
Certifications and compliances
Certifications obtained
Reference standards
11
1 changeover
AC1 - 8A 250V AC DC1 - 8A 30V DC
AC15 -1,5A 250V AC
300V AC
10
/ 10
operations
7
5
250V AC
7.3kV
imp
3kV
600V AC
9.8kV
imp
5.2kV
250V AC
7.3kV
imp
3kV
250V AC
7.3kV
imp
3kV
Towards relay
Towards
outputs and
Line1-2 inputs
AC supply
9.8kV
7.3kV
imp
5.2kV
3kV
-30 ÷ +70°C
-30 ÷ +80°C
<80% (IEC/EN 60068-2-78)
Degree 2
3
III
Z/ABDM (IEC/EN 60068-2-61)
15g (IEC/EN 60068-2-27)
0.7g (IEC/EN 60068-2-6)
Removable screw-type
0.2÷2.5 mm
(24÷12 AWG)
2
0.5 Nm
Flush mount
Polycarbonate
IP65 on front,
IP20 on terminals
680g
EAC
IEC/EN 61010-1, IEC/EN 61000-6-2
IEC/ EN 61000-6-3, IEC/ EN 60947-6-1*
*Other ATSE requirements are under consideration
such as closed transition TSE (make before break
transfer operation).
Towards DC
logic
7.3kV
3kV

Publicidad

loading