4. Digital Display
6
2-Digit Display: This display indicates which display mode is selected: Source Input Phase
(A# or b#), % Unbalanced (Ub), Output Circuits (C#), Total Output Power (OP), Temperature
(tC or tF), or Fault Code (FC).
Source A Phases (A#): Displays measurements for Source A. They include phase current
(A), Voltage (V) and Frequency (Hz).
Source B Phases (b#): Displays measurements for Source B. They include phase current
(B), Voltage (V) and Frequency (Hz).
% Unbalanced (Ub): The display shows the unbalanced load percentage deviance from the
average measured value. The percentage for the phase with the highest deviance is displayed.
Output Circuits (C#): Displays measurements for Output Circuit. They include Current (A),
Kilowatts (kW), Voltage (V) and Power Factor (PF).
Total Output Power (OP): Displays total power on all output circuits.
Temperature (t): The ambient temperature is displayed when this option is selected. The
temperature is displayed in Celsius by default, but can be switched to Fahrenheit.
Fault Code (FC): The Fault Code will only display if a breaker has tripped.
7
Mode Button: Scroll through the Display and Config menus using this button. Display menu
choice is shown on 2-digit display. Config menu choice is shown on 3-digit display.
8
SNMP Reset Button: Press the reset button for three seconds to reboot the ATS network
card. Rebooting the network card will not erase network settings or interrupt AC power. The
reset button is recessed. Use a paper clip or other suitable object to perform a reset.