Descargar Imprimir esta página

Ecoflam MULTIFLAM 300.1 Manual Del Usuario página 25

Quemadored mixtos gas/fuel pesado

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 59
SELECTOR
COMMUTATORE
AUTO
0
operating elements locked in an intermediate
0 = bloccaggio degli apparati per il
position
funzionamento in una posizione intermadia
operation on maximum capacity
= funzionamento alla massima potenza
= funzionamento alla minima potenza
operation on minimum capacity
AUTO = funzionamento automatico
automatic operation
ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS
Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas flow,
as established by analyzing the combustion process.
ADJUSTING THE MAXIMUM CAPACITY OF THE GAS
Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the gover-
nor.
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.
ADJUSTING THE INTERMEDIATE BURNER CAPACITY
Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.
AIR AND GAS ADJUSTMENT
Part. 1
-
-
+
Part. 2
ADJUSTING THE MAXIMUM AIR FLOW RATE
FIRING HEAD SETTING
-
+
420010309500 Multiflam 300.1 - 400.1 PR/PR
25
EN
- -
+
Part. 3

Publicidad

loading

Este manual también es adecuado para:

Multiflam 400.1