Installation
7. Power Supply: Pump is designed for 115 V., 60 Hz.,
operation and requires a minimum 15 amp individual
branch circuit. Both pump and switch are supplied
with 3-wire cord sets with grounding-type plugs.
Switch plug is inserted directly into outlet and pump
plug inserts into opposite end of switch plug.
kill. Pump should always be electrically grounded to a
suitable electrical ground such as a grounded water pipe
or a properly grounded metallic raceway, or ground wire
system. Do not cut off round ground pin.
8. If pump discharge line is exposed to outside sub-
freezing atmosphere, portion of line exposed must be
installed so any water remaining in pipe will drain
to the outfall by gravity. Failure to do this can cause
water trapped in discharge to freeze which could
result in damage to pump.
9. After piping, check valve and float switch have been
installed, the unit is ready for operation.
10. Secure power cords to the discharge pipe so they are
out of the way for proper float switch operation, prior
to testing the unit.
11. Check the pump operation by filling sump with water
and observing pump operation through one complete
cycle. For switch settings see the Electrical and
Switch Specifications chart.
and/or property damage. Failure to make this operational
check may lead to improper operation, premature failure,
and flooding.