Optional Installation
External Battery Connection
3
(Select Models)
Your UPS comes with a robust internal
battery system;
needed only to extend runtime. Adding
external batteries will increase recharge time
as well as runtime. This UPS supports
BP24V15RT2U (limit 1), BP24V28-2U (limit
1) and BP24V70-3U (multi-pack).
The illustration (see
you will insert the battery pack cable. Complete installation instructions for your battery pack
appear in the battery pack owner's manual. Make sure that cables are fully inserted into their
connectors. Small sparks may result during battery connection; this is normal.
Do not connect or disconnect battery packs when the UPS is running on battery power.
CAUTION! When an external battery pack is connected, make sure the AC load does not
exceed the nameplate rating. Select models are derated when an external battery pack
is connected. See UPS nameplate label for derating details.
When connecting external batteries to the UPS, go to the Tripp Lite website at www.tripplite.
com/en/support/bpcon g/index.cfm to download the External Battery Pack Utility software to
con gure your UPS for external battery support.
Model Name
SMART1000RM2U
SMART750RMXL2U
Note:
1. The runtime will automatically recalculate once the External Battery Pack Tool process is complete.
2. If the setup will no longer include external batteries, the UPS can be con gured to work without external
batteries via the LCD Screen. See External Battery Settings Control section under Basic Operation for details.
3. If external battery packs are removed, the UPS must be reset to "NO EXTERNAL BATTERY" via the LCD
interface or the External Battery Con guration Program available on the Tripp Lite website. Failure to do so
may result in damage to the internal batteries due to over-charging.
201205048 93-3149.indb 8
continued
external batteries are
) shows the location of your UPS's External Battery Connector
3
Wattage with Internal
Batteries Only
3
Wattage with External
800W
600W
8
A
where
A
Batteries Attached
N/A
450W
6/19/2012 11:33:37 AM