VCC-20-P CONDENSATE PUMP
for Plenum Applications
The VCC-20-P pump is designed to be used in plenum applications and is compliant with UL standard
UL2043, "Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed
in Air-handling Spaces."
This condensate pump automatically removes condensate water that drips from an air
conditioner evaporator coil, refrigeration equipment coil, condensing furnace, or con-
densing boiler. The pump is controlled by a float switch mechanism, which automatically
starts and stops the pump.
The pump also includes an auxiliary high-water level switch. This switch is configured to
open a thermostat circuit in the event of high water level in the pump reservoir, thereby
stopping production of condensate. Alternatively, this switch can be reconfigured by the
installer to close a circuit in the event of high water level, which operates an external alarm
or relay, (purchased separately).
Please examine your item(s) carefully to ensure that no damage occurred during shipment. If damage has
occurred, please contact the place of purchase. They will assist you in replacement or repair, if required.
This product is covered by a Limited Warranty for a period of 12 months from the date of original purchase by the
consumer. For complete warranty information, refer to www.LittleGiant.com.
Specifications
Model
VCC-20-P
VCC-20-P
SAFETY INSTRUCTIONS
Before Getting Started
This equipment should be installed and serviced by technically
qualified personnel who are familiar with the correct selection
and use of appropriate tools, equipment, and procedures. Failure
to comply with national and local electrical and plumbing codes
and within Little Giant recommendations may result in electrical
shock or fire hazard, unsatisfactory performance, or equipment
failure.
Know the product's application, limitations, and potential haz-
ards. Read and follow instructions carefully to avoid injury and
property damage. Do not disassemble or repair unit unless
described in this manual.
Refer to product data plate(s) for additional precautions, operat-
ing instructions and specifications.
Failure to follow installation or operation procedures and all
applicable codes may result in the following hazards:
Volts
HZ
115
60
230
50/60
Amps
Watts
Shut Off
1.5
75
20' (6.1 m)
0.6/0.5
58/60
17' (5.2 m)
Risk of death, personal injury, or
property damage due to explosion, fire,
or electric shock.
Do not use to pump flammable or explosive fluids such as
gasoline, fuel oil, kerosene, etc.
Do not use in explosive atmospheres or hazardous loca-
tions as classified by the NEC, ANSI/NFPA70.
Do not handle a pump or pump motor with wet hands or
when standing on a wet or damp surface, or in water.
When a pump is in its application, do not touch the motor,
pipes, or water until the unit is unplugged or electrically
disconnected.
If the power disconnect is out of sight, lock it in the open
position and tag it to prevent unexpected application of
power.
If the disconnect panel is not accessible, contact the elec-
tric company to stop service.
EN
English
Owner's Manual

Publicidad

Tabla de contenido
loading

Resumen de contenidos para Little Giant VCC-20-P

  • Página 1 Owner's Manual for Plenum Applications The VCC-20-P pump is designed to be used in plenum applications and is compliant with UL standard UL2043, “Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-handling Spaces.”...
  • Página 2: Before Getting Started

    SAFETY INSTRUCTIONS Before Getting Started Risk of severe injury or death by Risk of bodily injury, electric shock, electrical shock. or equipment damage. • To reduce risk of electrical shock, disconnect power before • This equipment must not be used by children or persons working on or around the system.
  • Página 3: Physical Installation

    INSTALLATION Physical Installation INSTALLATION Physical Installation Risk of damage to pump or other equipment. • There is a plastic plug inserted in the inlet opening beneath the conduit connector. Do not remove this plug and do not use this inlet opening. Install the pump on a flat surface.
  • Página 4: High Water Level Switch Connection

    INSTALLATION Electrical Connections A conduit connector is included for using 1/2” flexible metal conduit. Local and national codes require indi- vidual electrical conductors to be placed inside approved electrical conduit material such as FMC (flexible metal conduit). Check with local and national electric codes for proper selection and use of electrical con- duit.
  • Página 5: Operation Testing

    MAINTENANCE Operation Testing • Remove the pump’s motor cover (4). • Support the switch and carefully change the lead wire from the NO terminal to the NC terminal (3). • Re-install the motor cover. • Connect the switch leads in series with the low voltage external component as specified in the component’s manual.
  • Página 6: Troubleshooting

    Troubleshooting Problem Probable Causes Corrective Action Pump is not connected to electrical power. Connect pump to a dedicated GFCI circuit. Circuit breaker off or fuse removed. Turn on circuit breaker or replace fuse. Accumulation of debris or build-up on float. Clean float; a dirty float could be too heavy to operate correctly. Pump does not start when tank is full of condensate Remove the tank.
  • Página 7: Especificaciones

    Manual del propietario para applications de plénum La bomba VCC-20-P está diseñada para ser utilizada en aplicaciones plenum y cumple con la norma UL UL2043, “Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-han- dling Spaces.”...
  • Página 8 INSTRUCCIONES SOBRE SEGURIDAD Antes de empezar Riesgo de lesiones graves o muerte Riesgo de lesiones corporales, por descarga eléctrica. descargas eléctricas o daños al equipo. • Para reducir el riesgo de descarga eléctrica, desconecte la energía antes de trabajar en el sistema o cerca de él. Es posible •...
  • Página 9: Instalación

    INSTALACIÓN Installation fisica INSTALACIÓN Installation fisica Riesgo de daños a bomba u otros equipos. • Hay un tapón de plástico en el orificio de entrada debajo del conector del conducto. No quite este tapón y no use este orificio de entrada. Instale la bomba sobre una superficie plana.
  • Página 10: Cableado Del Interruptor Auxiliar De Nivel De Agua Alto

    INSTALACIÓN Conexiones eléctricas Se incluye un conector de conducto para usar un conductor metálico flexible de 1,27 cm (0,5 in). Las regulaciones locales y naciona- les exigen que los conductores eléctricos individuales se coloquen dentro de un material aprobado, como un FMC (conductor metálico flexible).
  • Página 11: Prueba De Operación

    MANTENIMIENTO Prueba de operación • Sostenga el interruptor y cuidadosamente cambie el cable conductor superior del terminal “NO” (2) al terminal “NC” (3). • Vuelva a instalar la cubierta del motor de la bomba. • Conecte los cables del interruptor en serie con el circuito de bajo voltaje del componente externo, tal como se especifica en el manual del componente.
  • Página 12: Solución De Problemas

    Solución de problemas Problema Causas probables Acción correctiva La bomba no está conectada a la alimentación. Conecte la bomba a un circuito GFCI dedicado. Disyuntor apagado o sin fusible. Encienda el disyuntor o reemplace el fusible. Acumulación de residuos o acumulación sobre Limpie el flotante;...
  • Página 13 La pompe VCC-20-P est conçue pour être utilisée dans les applications plénum et est conforme à la norme UL2043 « Fire Test for Heat and Visible Smoke Release for Discrete Products and Their Accessories Installed in Air-handling Spaces.
  • Página 14 CONSIGNES DE SÉCURITÉ Avant de commencer Risque de blessure grave ou de mort par Risque de blessure, de choc électrocution. électrique ou de dégâts matériels. • Pour réduire le risque de choc électrique, débranchez l’alimenta- • Cet équipement ne doit pas être utilisé par des enfants ou des tion avant de travailler sur le système ou autour de celui-ci.
  • Página 15: Installation Physique

    INSTALLATION Installation Physique INSTALLATION Installation Physique Risque de dommages à la pompe ou d’autres équipements. • Un bouchon de plastique est inséré dans l’orifice d’aspiration situé sous le raccord de conduit. Ne pas retirer le bouchon et ne pas utiliser cet orifice. Installer la pompe sur une surface plane.
  • Página 16 INSTALLATION Connexions électriques Un connecteur de conduit est inclus pour y raccorder un conduit métallique flexible de ½ po. Les codes locaux et nationaux exigent que les conducteurs électriques individuels soient insérés dans un conduit de câbles dont le matériau est approuvé, un conduit métallique flexible par exemple.
  • Página 17: Test De Fonctionnement

    INSTALLATION Test de fonctionnement • Connecter les fils de connexion de l’interrupteur au circuit à faible voltage du composant externe comme le recommande le manuel le composant. Accoler l’étiquette « ATTENTION TECHNICIEN D’ENTRETIEN » fournie avec la pompe bien visiblement à l’extérieur du panneau d’accès.
  • Página 18 INSTALLATION ENTRETIEN ENTRETIEN Risque de blessures corporelles ou de dommages matériels. • Ne pas laisser le réservoir déborder pendant les travaux d’entretien. • Inspecter et tester l’état et le fonctionnement de la pompe de relevage de condensats tous les six mois (plus fréquemment en cas d’utilisation intensive).
  • Página 19: Dépannage

    INSTALLATION Dépannage Dépannage Problème Causes probables Mesure corrective La pompe n’est pas branchée à l’alimentation Raccordez la pompe à un circuit dédié équipé d’une prise DDFT. électrique. Le disjoncteur est éteint ou le fusible a été Mettez le disjoncteur sous tension ou remplacez le fusible. retiré.
  • Página 20 Pour l’aide technique, entrez s’il vous plaît en contact : 800.701.7894 | littlegiant.com Franklin Electric Co., Inc. | Oklahoma City, OK 73157-2010 Form 998922 Rév. 003 06/19 Droits d’auteur © 2019, Franklin Electric, Co., Inc. Tous droits réservés.

Tabla de contenido