Wall Mount Indoor Unit; Part 1: General; Part 2: Installation Requirements - Haier ADVANCED Serie Guía De Especificaciones

Ocultar thumbs Ver también para ADVANCED Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

OUTDOOR UNIT
Part 3: Components (continued)
3.9 Copper Piping
A. All internally connected copper tubing shall conform to ASTM B280 tubing tolerances.
3.10 Outdoor Enclosure Materials
A. The outdoor cabinet shall be constructed of commercial grade DC51/DC52 hot-dip galvanized steel with
coating.
3.11 Defrost
A. The outdoor unit shall have a reverse-cycle (hot gas) defrost system to maximize heat pump operation and
minimize energy consumption.
3.12 Accumulator
A. The accumulator shall be connected to the compressor return line to prevent liquid refrigerant from entering
the compressor during operation.

WALL MOUNT INDOOR UNIT

Part 1: General

1.1 Description
A. The wall mounted indoor section completes the system when connected to the matching outdoor unit and
field-supplied piping and wiring.
1.2 Warranty
A. The wall mounted indoor unit shall be covered by a manufacturer's parts warranty. See Appendix for detail.
1.3 Sound Pressure Rating

Part 2: Installation Requirements

2.1 Condensate
A. The wall mouted indoor shall be shipped with a insulated polyethylene condensate tubing (5/8" ID) attached
from the factory.
B. The wall mounted indoor unit shall ship with a 6.5 ft (2m) corrugated drain tube that connects to the insulated
drain tube.
C. The wall mounted indoor unit shall be a gravity drain.
2.2 Clearances
A. The installer must follow the minium clearances illustrated in the Installation Manual when installing the indoor
unit.
2.3 Mounting
A. The wall mounted indoor unit shall ship with a galvanized metal wall bracket.
B. The wall bracket shall have multiple anchor points to provide the installer with many options to firmly attach the
wall mounted indoor unit to the wall.
C. The field-supplied mounting hardware must be sufficient to adequately support the indoor unit.
10
Model
Blower Pressure Sound Rating dB(A)
(Turbo/High/Medium/Low/Quiet)
AW09ES2VHB
44/40/35/31/23
AW12ES2VHB
45/41/36/32/23
AW15ES2VHB
48/46/42/36/34
AW18ES2VHB
48/46/42/36/34
AW24ES2VHB
49/47/42/36/34
31-5000411 Rev. 0