WIKA IS-3 Manual De Instrucciones página 65

Transmisor de presión
Ocultar thumbs Ver también para IS-3:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Annexe 2 : Dessin de contrôle FM, CSA
Alexander Wiegand SE & Co. KG
Hazardous (Classified) Location
Non-Incendive Installation
Class I, Zone 2, Group IIC
Class I, Division 2, Groups A, B, C and D
Class II, III, Div. 2, Groups F, G
(Note 2)
IS-3
Non-incendive Parameters:
Vmax / Ui = 30 V, Imax / Ii = 100 mA at Tamb ≤ 85 °C, Imax / Ii = 87 mA at Tamb > 85 °C, Pmax / Pi = 0.8 W
Ci = 16.5 nF (Flying Leads: + 0.2 nF/m), Li = 0 µH (Flying Leads: + 2 µH/m)
Notes:
1. The non-incendive field wiring concept allows the interconnection of two devices with non-incendive parameters not specifically examined in combination as a system when:
Uo or Voc ≤ Vmax, Io or Isc ≤ Imax, Ca or Co ≥ Ci + Ccable, La or Lo ≥ Li + Lcable, Po ≤ Pi.
2. Dust-tight conduit seal must be used when installed in Class II and Class III environments.
3. Control equipment connected to the Associated Apparatus must not use or generate more than 250 Vrms or Vdc.
4. Installation should be in accordance with the Canadian Electrical Code (CEC) Part I for Canada or the National Electrical Code
5. The configuration of Associated Apparatus must be under entity or non-incendive field wiring concept and - for the USA - FM Approved.
6. Associated Apparatus manufacturer`s installation drawing must be followed when installing this equipment.
7. Special Condition of use: Potential Electrostatic Charging Hazard - Parts of the enclosure may be constructed from plastic. To prevent the risk of electrostatic sparking the plastic
surface should be cleaned only with a damp cloth.
8. No revision to this drawing without prior approval by CSA and/or FM.
Mode d'emploi transmetteur de pression, type IS-3
Control drawing type IS-3
Non-Hazardous Location
Associated Apparatus
(Note 5), (Note 6), (Note 7)
Revision
03
02
01
31.05.2017
Drawing no.
14137236.01
Page 2 of 4
Control Equipment
(Note 3)
(ANSI/NFPA70) Sections 504 and 505 for USA.
®
created
Date
31.05.2017
Department
IN-RD-M
By
Jens Wagner
FR
checked
04.07.2017
PI-RD-CA
Frank Ballweg