Operation (cont'd)
Settings Table
Leakage Current Trip Point
Trips at 3 mA
Trips at 5 mA
Trips at 6 mA (5708-I only)
Trips at 7 mA
Trips at 10 mA
Trips at 30 mA (5708 only)
Does not trip.
7.
Plug the unit into every receptacle on the circuit, including all
remotely connected receptacles on all branches that are in series
with the GFCI. Using the procedure detailed above, verify that every
receptacle is properly wired to and protected by the GFCI.
10
GFCI Condition
GFCI is oversensitive.
GFCI is acceptable.
GFCI is acceptable.
GFCI is acceptable.
GFCI is faulty. REPLACE THE GFCI.
GFCI is faulty. REPLACE THE GFCI.
GFCI is faulty, or it was wired incorrectly
when it was installed. Have a qualified
electrician verify that it was installed
and wired according to the GFCI
manufacturer's instructions. If the GFCI
still does not trip, REPLACE THE GFCI.