Phase Sequence Indicator - Greenlee 5702 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Specifications

5702 Phase Sequence Indicator

Phase Indication: 3 lamps — L1, L2 and L3
Rotational Field Indication: 2 lamps
Voltage Range (line to line):
Rotational Field: 80 V to 440 V
Phase: 190 V to 600 V
Duty cycle: 20 sec. ON (max), 60 sec OFF (min)
Frequency: 50 Hz to 60 Hz
Current Load: < 3.5 mA
Overvoltage Category: Category III, 600 Volts
Pollution Degree: 2
Operating/Storage Conditions:
0 °C to 31 °C (32 °F to 88 °F), 0% to 80% relative humidity
31 °C to 45 °C (88 °F to 113 °F), relative humidity decreasing linearly from
80% to 50% (non-condensing)
Indoor use only
Altitude: 2000 m (6500')
Protection Category: IP 40
5123 Motor Rotation Indicator
Operating/Storage Temperature Range: 0 °C to 40 °C (32 °F to 104 °F)
Remove battery
Battery: 9-Volt (NEDA 1604, JIS 006P or IEC 6F22)
Do not connect the 5123 unit to live voltage.
Failure to observe this precaution can result in injury and can damage
the unit.
12

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

5123

Tabla de contenido