Select The Installation Locations - Hisense AST-09UW4RXETQ00B Instrucciones De Uso E Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installation instructions

Select the installation locations

Location for Installing Outdoor Unit
Where it is convenient to install and well ventilated.
Avoid installing it where flammable gas could leak.
Keep the required distance apart from the wall.
The pipe length between indoor and outdoor unit should be notmore than 5 meters in factory default
status, but it can go up to maximum 15 meters with additional refrigerant charge.
Keep the outdoor unit away from greasy dirt,vulcanization gas exit.
Avoid installing it by the roadside where there is a risk of muddy water.
A fixed base where it is not subject to increased operation noise.
Where there is not any blockage of the air outlet.
Avoid installing under direct sunlight, in an aisle or sideway, or near heat sources and ventilation fans.
Keep away from flammable materials, thick oil fog, and wet or uneven places.
Indoor unit
Max. allowed pipe length
Model
without additional
refrigerant (m)
7K~18K
21K 25K
~
28K~36K
If the height or pipe length is out of the scope of the table, please consult the merchant.
Pipe length is
15 meters Max.
Outdoor unit
Limit of
pipe
length (m)
5
15
5
15
5
15
Pipe length is
15 meters Max.
Indoor unit
Limit of Elevation
Difference H (m)
5
5
5
14
Outdoor unit
Required amount of
additional refrigerant (g/m)
20
30
40

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido