10. Standards

• Primary switched-mode power supply according to UL 60950, UL 508
• Security: EN 60950-1, EN 61558-2-16
• EMC: 61204-3
• Approvals: UL/CSA60950, UL508, DNV GL, EAC

11. Operating instructions

The cooling of the equipment must not be impaired. An unobstructed air supply and
a minimum distance of 15 mm to adjacent parts must be guaranteed.
The wiring of the connection terminals may only be carried out in a de-energised state.
Due to the protection class of IP 20, the device must be operated in dry rooms only.

12. Assembly/disassembly

Caution!
The system power supply must be operated as a SELV circuit only. As a result, the
system line must not be earthed at any point.
Mounting on top-hat rail TH35
12.1 Hook the power supply unit onto the top (a) of a 35 mm top-hat rail according to
EN 50022.
12.2 Press the power supply unit down against the top-hat rail until the lug (b) engages.
When lining up modules, a minimum distance of 15 mm must be maintained.
Dismantling of mounting rail
12.3 Pull the tab (b) down and unhook the power supply unit at the bottom.
12.4 Pull the power supply unit upwards.

13. Connection

The power supply should be installed in a separate room outside the wet area and
secured with a residual current device (RCD).
Connection input/output (spring-loaded terminal) max. 2.5 mm².
13.1 Check the operating voltage (see the identification plate) before connecting the
power supply unit.
13.2 Connect the power supply to the Input L and N terminals (a).
13.3 Connect the taps to the Output + and - terminals (b).
If the output voltage is present, the LED lights up.