2.
Transport, installation
and operating instructions
These instructions apply for the CEMO UNI-/MULTI-Tank 400 l
in accordance with the general construction inspection approval
Z-40.21-365.
The CEMO UNI-/MULTI-Tanks are supplied as a unit
with an impact-proof cover of recyclable material held in
place by a shrink-wrap as protection during transportation.
The level indicator can be found in the cover on the tank
side. The tanks are fitted with a leak sensor in the works.
The base is already fitted in the works. The cover should
only be removed at the place of installation!
The approval certificate with transport, installation
and operating instructions, inspection declaration and
warranty document can be found in an envelope in a tank
connection piece.
The tanks may only be installed in a fully enclosed room.
An additional collecting room is not required!
The tank must be installed at least 1 m from any furnaces
(fireplaces, chimneys, connecting pieces).
The tanks may not be installed in
a) passages,
b) staircases,
c) generally accessible corridors,
d) on the roofs of residential buildings,
hospitals, office buildings and similar
buildings or in their attics,
e) offices,
f) in guest rooms and bars.
The tanks may only be filled with heating oil or diesel
fuel using a free inlet without a fixed connection of the
filling line.
Insert the level indicator in the upper connection piece.
The cap has to be removed beforehand, slide the union
nut over the indicator from below and screw the threaded
liner into place. Then fasten the level indicator by scre-
wing the union nut onto the connection piece using the
enclosed seal.
The tanks can also be connected with a fixed connection
for automatic removal via submerged-pumpsor pumps
with subsequent accumulator. In this case the systems
should be fitted with an automatic safety device to prevent
a siphon effect.
If operated with an automatic removal the tanks must be
adequately ventilated, e.g. through the use of an aeration
and ventilation insert (2") that can be mounted in the
existing threaded liner.
The overfill safety device with the order no. 7330 is availa-
ble as an accessory for storing nonflammable media and
the specified connection.
The leak sensor with the order no. 7391 is available as
an accessory for storing used lubricating, hydraulic or
thermal oils.
3.
Inspection declaration
Inspection declaration
for CEMO UNI- / MULTI-Tank 400 l
of high-density polyethylene and galvanised sheet
steel for the unpressurised storage of media
according to the general construction inspection
approval Z-40.21-365.
Article No.:
7536/7979
Tank content:
400 l
Test pressure:
0.3 bar
Approval number: Z-40.21-365
We confirm that the tank complies with the provisions
of the general construction inspection approval. The
construction and leak tests have been performed.
The Works Experts:
CHEMOWERK GmbH
GB
11