Advanced Confi Guration, Parameters [Par] - S&P CR-TEMP Manual Del Usuario

Tabla de contenido

Publicidad

4.4. ADVANCED CONFIGURATION, PARAMETERS [PAr]
Into parameter menu [PAr] you have Access to advanced values. Once accessed
to mentioned menu, the acronym [AP] will appear on the left side. The navigation
inside this menu is as follows:
By numbering and order of appearance, the following parameters can be mo-
difi ed:
1.
Operating mode (range: 0-3; by default: 2)
2. ON/OFF HEAT CONTROL: Air heater function
2.
Hysteresis (range: 0.5-5.0°C; by default: 1.0°C)
3.
Proportional band (without use)
4.
Integration time (without use)
5.
Minimum proportional output (without use)
6.
Maximum proportional output (without use)
7.
Hysteresis heater relay (without use)
8.
Proportional output response time (without use)
9.
Low temperature set point alarm (range: -20-20°C; by default: 0°C)
10. High temperature set point alarm (range: 25-80°C; by default: 60°C)
11. Remote stop contact (range: 0-1; by default: 0)
0: Remote stop activated when contact closed (NO contact)
1: Remote stop activated when contact opened (NC contact)
12. Alarm contact (range: 0-1; by default: 0)
0: Remote stop activated when contact closed (NO contact)
1: Remote stop activated when contact opened (NC contact)
13. Detection time open windows function (range: 0, 1-30min; by default:
10min)
0: Disabled function
Move backwards
Validate and move to the next parameter
Increase value
Reduce value
25

Publicidad

Tabla de contenido
loading

Tabla de contenido