Connection diagram
SSM SBM
1 2 3
4
5 6
7 8 9
L1
L2
L3
PE
9-pole terminal block
24 Volt:
1
Power supply
Digital 1:
2
Input 1
Digital 2:
3
Input 2
RS 485:
4
Line A
RS 485:
5
Line B
Analog input:
6
-10V to +10V
Analog input:
7
0-10V or 0-20mA
10V
8
Reference voltage output
9
Earth
4-pole terminal block
CFI:
Centralized fault indication
COI:
Centralized operation indication
Gebr. Becker GmbH & Co. Postfach 2500220 D-42238 Wuppertal Tel. (02 02) 6 97 - 0 Fax (02 02) 66 08 55 Service: Tel. (02 02) 6 97 - 1 71 Fax (02 02) 64 44 74
Mode switch
off
on
Assignment of the mode switch
For activating digital inputs or for the supply of external sensors. Maximum current load 50 mA.
This input enables the converter ( 24V ).
This input has start/stop function ( 24V ).
Interrogation of internal data
Interrogation of internal data
without function
This input is used for the FC control. It is possible to switch
from Volt to Ampère using mode switch 4.
This output can be used for connecting a potentiometer, with a load of 10V and 10mA.
The relay is switched as break contact and is activated when the FC is in the fault mode.
The relay is switched as make contact and is activated when the FC is in the operating mode.
OFF:
1:
linear characteristic U/F curve
ON:
quadratic characteristic U/F curve
2:
OFF:
local mod
ON:
USS-log
3:
OFF:
Control signal source built-in potentiometer
ON:
Control signal source analog input 1
OFF:
4:
Analog input 1 0...10V
ON:
Analog input 1 0...20mA input
(not activated)
(not activated)
(not activated)
(not activated)
input