FAULTS / SOLUTIONS
Here below you can find some causes and the possible solutions for some problems that could cause a fail-
ure to start or a bad working of the burner. A fault usually makes the lock-out lamp light which is situated
inside the reset button of the control box (11, fig. 1, page 1). When lock-out lamp lights the burner will attempt
to light only after pushing the reset button. After this if the burner functions correctly, the lock-out can be
attributed to a temporary fault. However, if lockout continues, you must determine the cause of the problem
and take the action illustrated in the tables below .

START-UP PROBLEMS

FAULTS
The burner does not
start when the limit
thermostat closes.
Burner runs normally
in the pre-purge and
ignition
cycle
and
locks
out
after
3 seconds ca.
Burner starts with an
ignition delay.
The burner does not
switch
into
the
nd
2
stage.
3312
POSSIBLE CAUSES
Lack of electrical supply.
Gas is not supplied.
The gas pressure switch does not
close the contact.
The connections in the control box
are wrongly inserted.
The
air
pressure
changed over to the operational po-
sition.
The phase-neutral connection is in-
verted
The wiring to the earth is lacking or
ineffective.
Ionisation probe has a ground fault or
is not in contact with flame, or there is
a break in its wiring to control box, or
there is a ground fault due to its insu-
lation being defective.
Ignition electrode is wrongly posi-
tioned.
Air output is too high.
Valve brake not open enough with
insufficient gas allowed through.
The air damper open is jammed.
nd
The 2
stage gas valve does not en-
ergise.
Check for voltage at L1-N terminals in
7-pin plug.
Check the conditions of the fuses.
Check that safety thermostat is not
lock out.
Check gate opening.
Make sure that valves have changed
over to open position and that there
are no short circuits.
Adjust it.
Check and connect completely all the
plugs.
switch
has
Replace the pressure switch.
Swap them over.
Make earth connection efficient.
Check right position and, if necessary,
adjust as indicated in the manual.
Restore electrical connection.
Replace faulty lead.
Adjust them according to the instruc-
tions in the manual.
Set the air output according to the
instructions of this manual.
Set correctly.
Check that it is working properly.
Check the precise electrical connection.
Valve broken: replace it.
Check the air damper opener works
properly.
14 GB
SOLUTION