Setting The Orp Setpoint; Forced Operation; Alarm - Pool Technologie ORP Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 18

5.4.3. Setting the ORP setpoint

Possible settings : from
Default setting :
1) Press and hold down the right-hand key, until the menu
2) Press the top or bottom key x times until menu
3) Confirm by pressing the right-hand key.
4) Select a setpoint with the top/bottom keys.
5) Confirm by pressing the right-hand key : the selected setpoint freezes briefly.
6) Press on the left-hand key : the default display reappears.

5.4.4. Forced operation

Possible settings : from
Default setting :
To activate forced operation :
1) Press and hold down the right-hand key, until the menu
2) Confirm by pressing the right-hand key.
3) Select a duration with the top/bottom keys.
4) Confirm by pressing the right-hand key : the timer countdown is displayed in real time.
To stop forced operation :
Press on the left-hand key : the default display reappears.

5.5. Alarm

Flashing
Fault detected
display
Deviation of + or - 400 mV
between the ORP
measurement and the
ORP setpoint for 48 hours
to
(from 200 to 900 mV, in steps of 10 mV).
to
(i.e. from 1 to 24 h, in steps of 1 h).
Automatic
action
immediate
Switching
off the
electrolyser
flashes.
flashes.
flashes.
Checks and solutions
Check the ORP measurement in the
swimming pool with a recent analysis kit.
Check that the [electrolyser + cell]
assembly is functioning correctly.
Check all the settings :
- Calibrating the ORP probe.
- ORP measurement adjustment.
- Setting the ORP setpoint.
- Forced operation not activated.
Dismissal
Press on the
right-hand key
8

Publicidad

Tabla de contenido
loading

Tabla de contenido