Configure the system
Page
title/sub-
Page title
menu
Home page
Type
Page
Line 2
Line 3
Line 4
Line 5
Filter
Filter s
Filter co
Optical
Baudrate
Parity
RS485232
Address
Baudrate
Parity
Ethernet
IP add
Subnet
Gateway
TCP IP Prt
Virt al x (x =
Enable
alarm
Variables
number)
Type
Latch
Start cond
On delay
Set 1
Set 2
Out link
Out logic
30
WM50 - Instruction manual | 26/04/2022 | CARLO GAVAZZI Controls SpA
Description
Measurement page type displayed
on access to measurement menu
and after 120 s of inactivity
With Type = PAGE, default page
selected
With Type = VArS, variable
according to row selected
With Type = VArS, third row variable
selected
With Type = VArS, forth row variable
selected
With Type = VArS, fifth row variable
selected
Interval of filter intervention with
respect to full scale (%)
Filter coefficient
Baud rate (kbps)
Parity
Modbus address
Baud rate (kbps)
Parity
IP address
Subnet mask
Gateway
TCP/IP port
Enable of alarm x
Variable controlled by the alarm
Alarm type
Alarm retention enabled
Behavior if in alarm conditions at
start-up
Alarm activation delay (s)
Alarm activation threshold or upper
window limit
Alarm deactivation threshold or lower
window limit
Associated digital output
Output activation logic
Values
VArS: row by row customized page
PAGE: default page
The available measurement pages, recognizable via the
units of measure for
Managed variable selection
Managed variable selection
Managed variable selection
Managed variable selection
From 0 to 100 ( 2 )
From 1 to 256 (2)
9.6/ 19.2/ 38.4/ 115.2
None/ Odd/ Even
From 1 to 247
9.6 / 19.2/ 38.4/ 115.2
None/ Odd/ Even
From 0.0.0.0 to 255.255.255.255 ( 192.168.0.1 )
From 0.0.0.0 to 255.255.255.255 ( 255.255.255.0 )
From 0.0.0.0 to 255.255.255.255
From 1 to 9999 ( 502 )
Yes/ No
All managed real-time variables
uP: up alarm
down: down alarm
in: alarm in window
out: alarm out of window
Yes/ No
Yes: does not signal the alarm
No: signals the alarm
From 0 to 3600
The unit of measurement and range of admissible values
depend on the controlled variable.
0: no output associated
From 1 to 6
AND/ OR