Features
Main line measurement precision (main unit)
From 0.05 In to Imax
From 0.01 In to 0.05 In
From Un min -20% to Un max + 15%
From Un min -20% to Un max + 15%
From 0.05 In to Imax (PF=0.5L, 1, 0.8C)
From 0.01 In to 0.05 In (PF=1)
From 0.1 In to Imax (sinϕ=0.5L, 0.5C) From 0.05 In to Imax
(sinϕ=1)
From 0.05 In to 0.1 In (sinϕ=0.5L, 0.5C)
From 0.02 In to 0.05 In (PF=1)
Power factor
Active energy
Reactive energy
THD
From 45 to 65 Hz
Channel and load measurement precision (TCD12)
From 0.1 lb to Imax
From 0.05 lb to 0.1 lb
From 0.1 lb to Imax (PF=1)
From 0.2 lb to Imax (PF=0.5L, 0.8C)
From 0.05 In to 0.1 lb (PF=1)
From 0.1 lb to 0.2 lb (PF=0.5L, 0.8.5C)
From 0.1 lb to Imax (sinϕ=1)
From 0.2 lb to Imax (sinϕ=0.5L, 0.5C)
Power factor
Active energy
THD
Optical port
Compatible accessories
Configuration parameters
Configuration mode
40
WM50 - Instruction manual | 26/04/2022 | CARLO GAVAZZI Controls SpA
Current
±(0.2% rdg + 2dgt)
±(0.5% rdg + 2dgt)
Phase-phase voltage
±(0.5% rdg +1dgt)
Phase-neutral voltage
±(0.2% rdg +1dgt)
Active and apparent power
±(0.5% rdg +1dgt)
±(1% rdg +1dgt)
Reactive power
±(1% rdg + 1 dgt)
±(1.5% rdg + 1 dgt)
±[0.001+0.5%(1 – PF rdg)]
Class 0.5S (EN62053-22)
Class 2 (EN62053-23)
±1%
Frequency
±0.1 Hz
Current
±(0.5% rdg + 2dgt)
±(1% rdg + 2dgt)
Active and apparent power
±(2% rdg +1dgt)
±(2.5% rdg +1dgt)
Reactive power
±(3% rdg + 2 dgt)
±(3% rdg + 1 dgt)
±[0.001+0.5%(1 – PF rdg)]
Class 2 (EN62053-21)
±1%
OptoProg
Baud rate (9,6/ 19,2/ 38,4/ 115,2 kbps)
l
Parity (None/ Odd/ Even)
l
Via keypad or UCS