Tripp-Lite S3M25-100kVA Manual Del Propietário página 34

Protocolo modbus de ups trifásico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Protocol Application
3.5 Holding Registers (Address: 4XXXX) Data Content
Holding Registers
Address
40001
40002
40003
40004
40005
40006
40007
40008
40009
40010
Bypass Frequency Tracking
40011
40012
40013
40014
40015
40016
40017
40018
40019
40020
40021
40022
Battery Low PreAlarm Time
40023
40024
40025
40026
40027
Float Volt Temperature Repair
40028
40029
40030
40101
40102
40103
40104
Table 3.5.1 User Setting
Content
UPS Rating Capability
Parallel ID
Module Number
Work Mode
System Voltage Level
Output Frequency Level
Parallel Amount
Parallel Redundancy
Switch Bypass times
M/S Alternate Cyc
Range
Bypass Volt Upper Limit
Bypass Volt Lower Limit
Invert-Volt Fine
Battery Number
Single Battery Volt
Battery Group
Boost Upper Limit Volt
Float Base Volt
EOD Volt
Single Battery Capability
Max Charge Current
Power Walk In
Boost Last Time
LBS Setting
Status Control Information
Parameter
Operating Mode
Off-Grid Inverter Power
Control Command 1
Control Command 2
Control Command 3
Baud Rate
Size
Range
2 Bytes
100~4000
2 Bytes
1~15
2 Bytes
1~20
2 Bytes
2 Bytes
110~240
2 Bytes
50, 60
2 Bytes
1~15
2 Bytes
0~14
2 Bytes
3~10
2 Bytes
1~6
2 Bytes
1, 2, 4, 5, 10
2 Bytes
5, 10, 15, 25
2 Bytes
-45, -30, -20
2 Bytes
-50~+50
2 Bytes
13~20
2 Bytes
2, 4, 6, 12
2 Bytes
1~8
2 Bytes
230~240
2 Bytes
220~229
2 Bytes
120~190
2 Bytes
1~2000
2 Bytes
1~100
2 Bytes
1~25
2 Bytes
0~20
2 Bytes
0~999
2 Bytes
0, 1, 2
2 Bytes
2 Bytes
1~6
2 Bytes
2 Bytes
2 Bytes
2 Bytes
9600, 14400,
2 Bytes
19200
34
Unit
Remark
0.1kVA
Table 4.4.2
V
Hz
month
%
1%, 2%, 4%, 5%, 10%
%
5%, 10%, 15%, 25%
%
-45%, -30%, -20%
node
V
group
0.01V/Cell
0.01V/Cell
0.01V/Cell
AH
minute
A
second
minute
0: LBS Disable;
1: LBS Primary;
2: LBS Replica
Table 4.3.9
0.001V/
Cell/ºC
Table 4.4.3
Self-Test Mode
Table 4.4.4
Table 4.4.5
Table 4.4.6