Isolate the UPS system before working on the circuit. An easily accessible disconnect device should be incorporated in the fixed wiring. The disconnect device must be a 4-pole device and must disconnect all line conductors and the neutral conductor. 200803004 93-2793 SU80k manual 4C.indd E4 200803004 93-2793 SU80k manual 4C.indd E4...
3 seconds to return the UPS system to online (normal) mode. Section 9 – Display and Configuration for detailed information about the control panel’s menus and displays. 200803004 93-2793 SU80k manual 4C.indd E6 200803004 93-2793 SU80k manual 4C.indd E6 6/16/2008 1:43:08 PM...
UPS system over longer distances. The casters are not designed to provide long-term support for the UPS system after final installation. Use the levelers to provide long-term support. 200803004 93-2793 SU80k manual 4C.indd E7 200803004 93-2793 SU80k manual 4C.indd E7...
Página 8
Controls AC input power to the UPS system during manual bypass operation. • Output Circuit Breaker Switch (Q4): Controls AC output power. 200803004 93-2793 SU80k manual 4C.indd E8 200803004 93-2793 SU80k manual 4C.indd E8 6/16/2008 1:43:09 PM 6/16/2008 1:43:09 PM...
Make sure the casters at the bottom of the unit are unlocked. Using extreme caution, slowly roll the unit down the ramp with the aid of several assistants. 200803004 93-2793 SU80k manual 4C.indd E9 200803004 93-2793 SU80k manual 4C.indd E9 6/16/2008 1:43:10 PM...
For emergency use, install a fire extinguisher rated for energized electrical equipment fires (Class C rating or exact equivalent, with a non-conductive extinguishing agent) near the UPS system. 200803004 93-2793 SU80k manual 4C.indd E10 200803004 93-2793 SU80k manual 4C.indd E10 6/16/2008 1:43:10 PM...
V >0, install an isolation transformer before the UPS system and input power source, then connect the UPS system’s “Neutral” and “Ground” together. 200803004 93-2793 SU80k manual 4C.indd E11 200803004 93-2793 SU80k manual 4C.indd E11 6/16/2008 1:43:11 PM...
AC input/output of the UPS system at this time, replace the terminal block cover of the UPS system. 200803004 93-2793 SU80k manual 4C.indd E14 200803004 93-2793 SU80k manual 4C.indd E14 6/16/2008 1:43:13 PM...
6-7, wiring the UPS systems as shown in the diagram. • Connect the included parallel redundancy cable to the parallel redundancy port of each UPS system. 200803004 93-2793 SU80k manual 4C.indd E16 200803004 93-2793 SU80k manual 4C.indd E16 6/16/2008 1:43:24 PM 6/16/2008 1:43:24 PM...
Warning: The UPS system must be de-energized completely before XFMR XFMR MAIN performing maintenance or repair by shutting it down completely after switching it to manual bypass mode. 200803004 93-2793 SU80k manual 4C.indd E17 200803004 93-2793 SU80k manual 4C.indd E17 6/16/2008 1:43:27 PM 6/16/2008 1:43:27 PM...
Similar to auto bypass mode for a single UPS system (Section 7-3), except with parallel (1+1) UPS systems. MAIN XFMR XFMR UPS1 LOAD MAIN XFMR XFMR UPS2 200803004 93-2793 SU80k manual 4C.indd E18 200803004 93-2793 SU80k manual 4C.indd E18 6/16/2008 1:43:27 PM 6/16/2008 1:43:27 PM...
Confirm that the manual bypass circuit breaker switch is off. Main Main Input Input Front Panel Front Panel Back Panel Back Panel 200803004 93-2793 SU80k manual 4C.indd E20 200803004 93-2793 SU80k manual 4C.indd E20 6/16/2008 1:43:27 PM 6/16/2008 1:43:27 PM...
The inverter will activate and use stored DC battery power to supply AC power to connected equipment. The “BATTERY” LED will illuminate. 200803004 93-2793 SU80k manual 4C.indd E21 200803004 93-2793 SU80k manual 4C.indd E21 6/16/2008 1:43:31 PM...
Switch off the main input circuit breaker switch Main Input Front Panel Back Panel • Switch off the bypass input circuit breaker switch Main Input Front Panel Back Panel 200803004 93-2793 SU80k manual 4C.indd E22 200803004 93-2793 SU80k manual 4C.indd E22 6/16/2008 1:43:34 PM 6/16/2008 1:43:34 PM...
For the UPS system you wish to shut down, switch off the main input circuit breaker switch , then switch off the output circuit breaker switch Main Input Front Panel Back Panel 200803004 93-2793 SU80k manual 4C.indd E24 200803004 93-2793 SU80k manual 4C.indd E24 6/16/2008 1:43:41 PM 6/16/2008 1:43:41 PM...
UPS system. The LCD screen will turn off completely. Main Input Front Panel Back Panel 200803004 93-2793 SU80k manual 4C.indd E25 200803004 93-2793 SU80k manual 4C.indd E25 6/16/2008 1:43:46 PM 6/16/2008 1:43:46 PM...
Página 26
(normal) Front Panel Back Panel mode at the same time. Main Input Front Panel Back Panel 200803004 93-2793 SU80k manual 4C.indd E26 200803004 93-2793 SU80k manual 4C.indd E26 6/16/2008 1:43:50 PM 6/16/2008 1:43:50 PM...
The UPS system is starting up from battery power. • The UPS system is in auto bypass mode. Connected equipment loads will lose power if the bypass power source fails. 200803004 93-2793 SU80k manual 4C.indd E28 200803004 93-2793 SU80k manual 4C.indd E28 6/16/2008 1:43:56 PM 6/16/2008 1:43:56 PM...
Página 29
UPS system. Connected equipment loads will lose power if the bypass power source fails. 200803004 93-2793 SU80k manual 4C.indd E29 200803004 93-2793 SU80k manual 4C.indd E29 6/16/2008 1:43:56 PM 6/16/2008 1:43:56 PM...
8 0 . 0 K V A / 6 4 . 0 K W 7 4 A 8 0 . 0 K V A / 6 4 . 0 K W 200803004 93-2793 SU80k manual 4C.indd E30 200803004 93-2793 SU80k manual 4C.indd E30 6/16/2008 1:43:56 PM...
SETUP”, then press the enter button ( • Use the scroll buttons ( , ) and the enter button ( ) to select “VOLTAGE RANGE” or “FREQUENCY RANGE”. 200803004 93-2793 SU80k manual 4C.indd E31 200803004 93-2793 SU80k manual 4C.indd E31 6/16/2008 1:43:57 PM 6/16/2008 1:43:57 PM...
From the “VOLTAGE” screen, use the scroll buttons ( , ) to select the desired setting and press the enter button ( to confirm the setting. 200803004 93-2793 SU80k manual 4C.indd E32 200803004 93-2793 SU80k manual 4C.indd E32 6/16/2008 1:43:57 PM...
SETUP”, then press the enter button ( • Use the scroll buttons ( , ) and the enter button ( ) to select one of the menu choices. 200803004 93-2793 SU80k manual 4C.indd E33 200803004 93-2793 SU80k manual 4C.indd E33 6/16/2008 1:43:58 PM 6/16/2008 1:43:58 PM...
Página 34
( , ) to select the desired setting and press the enter button ( to confirm the setting. Note: Press the “ESC” button to return to the previous menu. 200803004 93-2793 SU80k manual 4C.indd E34 200803004 93-2793 SU80k manual 4C.indd E34 6/16/2008 1:43:58 PM...
Note: If two UPS systems are used in a parallel redundancy configuration, the parallel ID numbers of the UPS systems must be 1 and 2. 200803004 93-2793 SU80k manual 4C.indd E35 200803004 93-2793 SU80k manual 4C.indd E35 6/16/2008 1:43:58 PM...
Use the scroll buttons ( , ) and the enter button ( ) to select a menu choice. 200803004 93-2793 SU80k manual 4C.indd E36 200803004 93-2793 SU80k manual 4C.indd E36 6/16/2008 1:43:58 PM 6/16/2008 1:43:58 PM...
You must enter the administrator password to confirm the reset operation. Note: Press the “ESC” button to return to the previous menu. 200803004 93-2793 SU80k manual 4C.indd E37 200803004 93-2793 SU80k manual 4C.indd E37 6/16/2008 1:43:59 PM 6/16/2008 1:43:59 PM...
You must enter the administrator password to confirm the reset operation. Note: Press the “ESC” button to return to the previous menu. 200803004 93-2793 SU80k manual 4C.indd E38 200803004 93-2793 SU80k manual 4C.indd E38 6/16/2008 1:44:00 PM 6/16/2008 1:44:00 PM...
10-9 Output Dry Contact Circuit Diagram The UPS system has six dry contact output connections. These contacts can be normally open or normally closed. OUTPUT CONTACT 200803004 93-2793 SU80k manual 4C.indd E44 200803004 93-2793 SU80k manual 4C.indd E44 6/16/2008 1:44:01 PM 6/16/2008 1:44:01 PM...
UPS system. Attempting to use an incompatible cable may damage the UPS systems and create a serious risk of personal injury and property damage. 200803004 93-2793 SU80k manual 4C.indd E45 200803004 93-2793 SU80k manual 4C.indd E45 6/16/2008 1:44:01 PM...
Ground Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Made in China. 200803004 93-2793 SU80k manual 4C.indd E47 200803004 93-2793 SU80k manual 4C.indd E47 6/16/2008 1:44:01 PM 6/16/2008 1:44:01 PM...
Todos los modelos soportan gabinetes para baterías externas para tiempo de respaldo extendido • Pantalla LCD de alta resolución simplifica la operación y entrega información operacional detallada incluyendo diagramas de bloque del sistema 200803004 93-2793 SU80k manual 4C.indd S50 200803004 93-2793 SU80k manual 4C.indd S50 6/16/2008 1:44:02 PM...
El dispositivo de desconexión debe ser un dispositivo de 4 polos y debe desconectar a todos los conductores de línea y el conductor neutro. 200803004 93-2793 SU80k manual 4C.indd S51 200803004 93-2793 SU80k manual 4C.indd S51 6/16/2008 1:44:03 PM...
Advertencias en la Instalación del Cableado Eléctrico • Vea la Sección 6-1 para Advertencias sobre la instalación del cableado eléctrico 200803004 93-2793 SU80k manual 4C.indd S52 200803004 93-2793 SU80k manual 4C.indd S52 6/16/2008 1:44:03 PM 6/16/2008 1:44:03 PM...
Vea la Sección 9 – Pantalla y Configuración para información detallada acerca del los menús del panel de control y las pantallas. 200803004 93-2793 SU80k manual 4C.indd S53 200803004 93-2793 SU80k manual 4C.indd S53 6/16/2008 1:44:03 PM 6/16/2008 1:44:03 PM...
UPS por largas distancias. Las ruedas no están diseñadas par proporcionar un soporte por largo tiempo al UPS después de la instalación final. Utilice los niveladores/puntales par proporcionar soporte a largo plazo. 200803004 93-2793 SU80k manual 4C.indd S54 200803004 93-2793 SU80k manual 4C.indd S54...
Página 55
4 – Características y Funciones del Panel Frontal y Trasero (continuación) Se muestra el SU80K (parte posterior) Nota: Los modelos Individuales pueden variar de los diagramas. Niveladores/Puntales: Los niveladores/puntales proporcionan soporte por largo tiempo al sistema UPS. Ruedas: Las ruedas están diseñadas para ajustes de posicionamientos pequeños dentro del área de ubicación final únicamente. No están diseñadas para mover el UPS por largas distancias.
Asegúrese de que las ruedas debajo de la unidad no están aseguradas. Extreme precauciones y con la ayuda de varios asistentes, lentamente ruede la unidad rampa abajo. 200803004 93-2793 SU80k manual 4C.indd S56 200803004 93-2793 SU80k manual 4C.indd S56 6/16/2008 1:44:05 PM...
Para casos de emergencia, instale cerca del sistema UPS un extintor certificado para incendios de equipos eléctricos (Certificado Clase C o su equivalente exacto con un agente extintor no conductivo). 200803004 93-2793 SU80k manual 4C.indd S57 200803004 93-2793 SU80k manual 4C.indd S57 6/16/2008 1:44:05 PM 6/16/2008 1:44:05 PM...
>0, instale un transformador de aislamiento antes del sistema UPS y la fuente de energía de entrada y entonces conecte el “Neutro y la “Tierra” del sistema UPS juntos. 200803004 93-2793 SU80k manual 4C.indd S58 200803004 93-2793 SU80k manual 4C.indd S58...
Gabinete de Baterías Externas – – Se muestran el SU80K y el BP480V40C únicamente como ilustración; consulte la documentación del gabinete de baterías para las especificaciones exactas 200803004 93-2793 SU80k manual 4C.indd S59 200803004 93-2793 SU80k manual 4C.indd S59...
Si no tiene planes de de cablear la entrada/salida CA del sistema UPS en este momento, vuelva a colocar la tapa del bloque de terminles del sistema UPS. 200803004 93-2793 SU80k manual 4C.indd S61 200803004 93-2793 SU80k manual 4C.indd S61 6/16/2008 1:44:07 PM...
UPS y crea un riesgo de lesiones personales y daños a la propiedad. • Vuelva a colocar la tapa del bloque de terminales del sistema the UPS. 200803004 93-2793 SU80k manual 4C.indd S62 200803004 93-2793 SU80k manual 4C.indd S62 6/16/2008 1:44:13 PM 6/16/2008 1:44:13 PM...
• Conecte el cable, incluido, de redundancia en paralelo al puerto de redundancia en paralelo de cada sistema UPS. 200803004 93-2793 SU80k manual 4C.indd S63 200803004 93-2793 SU80k manual 4C.indd S63 6/16/2008 1:44:18 PM 6/16/2008 1:44:18 PM...
PRINCIPAL MAIN debe desactivarse completamente antes de efectuar cualquier mantenimiento o reparación apagándola completamente después de cambiar a modo de derivación manual. 200803004 93-2793 SU80k manual 4C.indd S64 200803004 93-2793 SU80k manual 4C.indd S64 6/16/2008 1:44:21 PM 6/16/2008 1:44:21 PM...
Ambos sistemas UPS deben estar en Modo de Derivación Manual. PRINCIPAL MAIN XFMR XFMR UPS1 CARGA LOAD PRINCIPAL MAIN XFMR XFMR UPS2 200803004 93-2793 SU80k manual 4C.indd S66 200803004 93-2793 SU80k manual 4C.indd S66 6/16/2008 1:44:21 PM 6/16/2008 1:44:21 PM...
CD almacenada en la batería para suministrar energía CA al equipo conectado. El LED “BATTERY” [Batería] se iluminará. 200803004 93-2793 SU80k manual 4C.indd S68 200803004 93-2793 SU80k manual 4C.indd S68 6/16/2008 1:44:24 PM 6/16/2008 1:44:24 PM...
UPS. • Si los sistemas UPS tienen gabinetes de batearías externas conectadas encienda el interruptor de circuitos de cada módulo de baterías. 200803004 93-2793 SU80k manual 4C.indd S70 200803004 93-2793 SU80k manual 4C.indd S70 6/16/2008 1:44:30 PM 6/16/2008 1:44:30 PM...
El sistema UPS está en modo de derivación automática. Las cargas del equipo conectado perderán energía si la fuente de energía de la derivación falla. 200803004 93-2793 SU80k manual 4C.indd S75 200803004 93-2793 SU80k manual 4C.indd S75 6/16/2008 1:44:49 PM...
Página 76
UPS. Las cargas del equipo conectado perderán la energía si la fuente de la derivación falla. 200803004 93-2793 SU80k manual 4C.indd S76 200803004 93-2793 SU80k manual 4C.indd S76 6/16/2008 1:44:49 PM 6/16/2008 1:44:49 PM...
8 0 . 0 K V A / 6 4 . 0 K W 7 4 A 8 0 . 0 K V A / 6 4 . 0 K W 200803004 93-2793 SU80k manual 4C.indd S77 200803004 93-2793 SU80k manual 4C.indd S77 6/16/2008 1:44:49 PM...
Desde la pantalla “VOLTAGE”, use los botones de recorrido ( , ) para seleccionar el ajuste deseado y presione el botón entrar ( ) para confirmar el ajuste. 200803004 93-2793 SU80k manual 4C.indd S79 200803004 93-2793 SU80k manual 4C.indd S79 6/16/2008 1:44:50 PM 6/16/2008 1:44:50 PM...
Use los botones de recorrido ( , ) y el botón entrar ( ) para seleccionar una de las opciones del menú. 200803004 93-2793 SU80k manual 4C.indd S80 200803004 93-2793 SU80k manual 4C.indd S80 6/16/2008 1:44:50 PM 6/16/2008 1:44:50 PM...
Página 81
( , ) para seleccionar los ajustes deseados y presione el botón entrar ( ) para confirmar los ajustes. Nota: Presione el botón “ESC” para regresar al menú anterior. 200803004 93-2793 SU80k manual 4C.indd S81 200803004 93-2793 SU80k manual 4C.indd S81 6/16/2008 1:44:50 PM 6/16/2008 1:44:50 PM...
) para confirmar los ajustes. Nota: Si se usan dos sistemas UPS en configuración de redundancia en paralelo, Los números ID de paralelo de los sistemas UPS deben ser 1 y 2. 200803004 93-2793 SU80k manual 4C.indd S82 200803004 93-2793 SU80k manual 4C.indd S82 6/16/2008 1:44:50 PM...
Use los botones de recorrido ( , ) y el botón entrar ( ) para elegir una opción del menú. 200803004 93-2793 SU80k manual 4C.indd S83 200803004 93-2793 SU80k manual 4C.indd S83 6/16/2008 1:44:51 PM...
Debe introducir la contraseña del administrador para confirmar la operación de restauración. Nota: Presione el botón “ESC” para regresar al menú anterior. 200803004 93-2793 SU80k manual 4C.indd S84 200803004 93-2793 SU80k manual 4C.indd S84 6/16/2008 1:44:51 PM 6/16/2008 1:44:51 PM...
Debe introducir la contraseña del administrador para confirmar la operación de restauración. Nota: Presione el botón “ESC” para regresar al menú anterior. 200803004 93-2793 SU80k manual 4C.indd S85 200803004 93-2793 SU80k manual 4C.indd S85 6/16/2008 1:44:51 PM 6/16/2008 1:44:51 PM...
CD. El personal de servicio calificado puede querer ver esta información cuando esté efectuando mantenimiento o reparaciones al sistema UPS. Nota: Presione el botón “ESC” para regresar al menú anterior. 200803004 93-2793 SU80k manual 4C.indd S87 200803004 93-2793 SU80k manual 4C.indd S87 6/16/2008 1:44:52 PM 6/16/2008 1:44:52 PM...
El “interruptor de transferencia estático” [static transfer switch] (STS) de la derivación está funcionando de forma anormal. Nota: Si necesita habilitar mensajes opcionales, comuníquese con Tripp Lite. 200803004 93-2793 SU80k manual 4C.indd S90 200803004 93-2793 SU80k manual 4C.indd S90 6/16/2008 1:44:52 PM...
El sistema UPS tiene seis contactos de salida de contacto seco. Estos contactos pueden estar normalmente abiertos o normalmente cerrados. SALIDA DE CONTACTO SECO 200803004 93-2793 SU80k manual 4C.indd S91 200803004 93-2793 SU80k manual 4C.indd S91 6/16/2008 1:44:52 PM 6/16/2008 1:44:52 PM...
UPS. Intentar usar un cable incompatible puede dañar los sistemas UPS y crear un serio riesgo de lesiones personales o daños a la propiedad. 200803004 93-2793 SU80k manual 4C.indd S92 200803004 93-2793 SU80k manual 4C.indd S92...
Tierra La política de Tripp Lite es la de una mejora constante. Especificaciones sujetas a cambios sin previo aviso. Fabricado en China. 200803004 93-2793 SU80k manual 4C.indd S94 200803004 93-2793 SU80k manual 4C.indd S94 6/16/2008 1:44:52 PM 6/16/2008 1:44:52 PM...
Tous les modèles proposent des boîtiers de batterie externe pour un temps d’exécution prolongé sur batterie de secours. • L’écran d’état ACL à haute résolution simplifie l’opération et fournit des renseignements opérationnels détaillés, incluant les schémas fonctionnels du système. 200803004 93-2793 SU80k manual 4C.indd F97 200803004 93-2793 SU80k manual 4C.indd F97 6/16/2008 1:44:53 PM 6/16/2008 1:44:53 PM...
Isoler l’onduleur avant d’effectuer des travaux sur le circuit. Un dispositif de débranchement facilement accessible doit être incorporé dans le câblage fixe. Le dispositif de débranchement doit comporter 4 pôles et doit débrancher tous les conducteurs d’alimentation ainsi que le conducteur neutre. 200803004 93-2793 SU80k manual 4C.indd F98 200803004 93-2793 SU80k manual 4C.indd F98 6/16/2008 1:44:54 PM...
L’omission de recharger périodiquement les batteries peut causer des dommages irréversibles à la batterie. Avertissements concernant le câblage • Voir la Section 6-1 pour les avertissements concernant le câblage. 200803004 93-2793 SU80k manual 4C.indd F99 200803004 93-2793 SU80k manual 4C.indd F99 6/16/2008 1:44:54 PM 6/16/2008 1:44:54 PM...
Voir la Section 9 – Affichage et Configuration pour des renseignements détaillés à propos des menus et affichages du tableau de commande. 200803004 93-2793 SU80k manual 4C.indd F100 200803004 93-2793 SU80k manual 4C.indd F100 6/16/2008 1:44:54 PM 6/16/2008 1:44:54 PM...
Les roulettes ne sont pas conçues pour supporter l’onduleur à long terme après son installation définitive. Utiliser les vérins de calage pour supporter l’appareil à long terme. 200803004 93-2793 SU80k manual 4C.indd F101 200803004 93-2793 SU80k manual 4C.indd F101...
Página 102
Commutateur du disjoncteur d’entrée de dérivation (Q2) : Contrôle l’entrée du CA à l’onduleur pendant qu’il fonctionne en mode de dérivation automatique. 200803004 93-2793 SU80k manual 4C.indd F102 200803004 93-2793 SU80k manual 4C.indd F102 6/16/2008 1:44:56 PM 6/16/2008 1:44:56 PM...
Avec une extrême prudence, faire rouler l’appareil doucement sur la rampe, en vous faisant aider de plusieurs personnes. 200803004 93-2793 SU80k manual 4C.indd F103 200803004 93-2793 SU80k manual 4C.indd F103 6/16/2008 1:44:57 PM 6/16/2008 1:44:57 PM...
En cas d’urgence, installer un extincteur approuvé pour les incendies causés par l’appareillage électrique (de Classe C ou son équivalent exact, utilisant un agent extincteur non conducteur) près de l’onduleur. 200803004 93-2793 SU80k manual 4C.indd F104 200803004 93-2793 SU80k manual 4C.indd F104 6/16/2008 1:44:57 PM 6/16/2008 1:44:57 PM...
électrique, puis connecter ensemble le fil neutre et le fil de mise à la terre. 200803004 93-2793 SU80k manual 4C.indd F105 200803004 93-2793 SU80k manual 4C.indd F105 6/16/2008 1:44:57 PM...
– – Les modèles SU80K et BP480V40C sont montrés à titre d’illustration seulement; consulter la documentation du boîtier de la batterie pour obtenir les spécifications exactes. 200803004 93-2793 SU80k manual 4C.indd F106 200803004 93-2793 SU80k manual 4C.indd F106...
SU80K 120/208 V CA, 3Ø, 300 A 220 A 4/0 AWG 2 AWG 4-wire + ground, wye raccord en étoile 200803004 93-2793 SU80k manual 4C.indd F107 200803004 93-2793 SU80k manual 4C.indd F107 6/16/2008 1:45:00 PM 6/16/2008 1:45:00 PM...
Página 108
Si vous ne comptez pas procéder au câblage entrée/sortie CA de l’onduleur pour le moment, replacer le couvercle du bornier de l’onduleur. 200803004 93-2793 SU80k manual 4C.indd F108 200803004 93-2793 SU80k manual 4C.indd F108 6/16/2008 1:45:00 PM 6/16/2008 1:45:00 PM...
à N. Ne pas respecter la polarité endommagera l’onduleur et créera un risque sérieux de blessure et de dommages matériels. • Replacer le couvercle du bornier de l’onduleur. 200803004 93-2793 SU80k manual 4C.indd F109 200803004 93-2793 SU80k manual 4C.indd F109 6/16/2008 1:45:05 PM 6/16/2008 1:45:05 PM...
6-7, pour câbler l’onduleur tel que montré dans le schéma. • Brancher le câble parallèle de redondance inclus au port parallèle de redondance de chaque onduleur. 200803004 93-2793 SU80k manual 4C.indd F110 200803004 93-2793 SU80k manual 4C.indd F110 6/16/2008 1:45:10 PM 6/16/2008 1:45:10 PM...
Avertissement : L’onduleur doit être mis complètement hors tension avant d’effectuer un entretien soit une réparation en l’éteignant complètement après être passé en mode de dérivation manuelle. 200803004 93-2793 SU80k manual 4C.indd F111 200803004 93-2793 SU80k manual 4C.indd F111 6/16/2008 1:45:13 PM 6/16/2008 1:45:13 PM...
être mis en mode de dérivation manuelle. PRINCIPAL MAIN XFMR XFMR ONDULEUR1 UPS1 CHARGE LOAD PRINCIPAL MAIN XFMR XFMR ONDULEUR2 UPS2 200803004 93-2793 SU80k manual 4C.indd F113 200803004 93-2793 SU80k manual 4C.indd F113 6/16/2008 1:45:13 PM 6/16/2008 1:45:13 PM...
Vérifier que le commutateur du disjoncteur de dérivation manuelle est en position fermée. Main Input Entrée Entrée de Dérivation Sortie principale dérivation manuelle Panneau Arrière Panneau Avant 200803004 93-2793 SU80k manual 4C.indd F114 200803004 93-2793 SU80k manual 4C.indd F114 6/16/2008 1:45:14 PM 6/16/2008 1:45:14 PM...
CC emmagasiné dans la batterie pour alimenter les appareils qui y sont branchés en CA. Le TÉMOIN DEL « BATTERY » s’illuminera. 200803004 93-2793 SU80k manual 4C.indd F115 200803004 93-2793 SU80k manual 4C.indd F115 6/16/2008 1:45:16 PM...
Si l’onduleur est connecté à des boîtiers de batterie externe, allumer le commutateur du disjoncteur du boîtier de la batterie externe de chaque bloc-batterie. 200803004 93-2793 SU80k manual 4C.indd F117 200803004 93-2793 SU80k manual 4C.indd F117 6/16/2008 1:45:22 PM 6/16/2008 1:45:22 PM...
L’onduleur est en mode de dérivation automatique. Les appareils qui y sont branchés perdront leur alimentation si la source d’alimentation électrique de dérivation tombe en panne. 200803004 93-2793 SU80k manual 4C.indd F122 200803004 93-2793 SU80k manual 4C.indd F122 6/16/2008 1:45:41 PM...
Página 123
Les appareils qui y sont branchés perdront leur alimentation si la source d’alimentation électrique de dérivation tombe en panne. 200803004 93-2793 SU80k manual 4C.indd F123 200803004 93-2793 SU80k manual 4C.indd F123 6/16/2008 1:45:41 PM 6/16/2008 1:45:41 PM...
8 0 . 0 K V A / 6 4 . 0 K W 7 4 A 8 0 . 0 K V A / 6 4 . 0 K W 200803004 93-2793 SU80k manual 4C.indd F124 200803004 93-2793 SU80k manual 4C.indd F124 6/16/2008 1:45:41 PM...
Utiliser les touches de défilement ( ) et la touche d’entrée ) pour sélectionner « VOLTAGE RANGE» ou « FREQUENCY RANGE ». 200803004 93-2793 SU80k manual 4C.indd F125 200803004 93-2793 SU80k manual 4C.indd F125 6/16/2008 1:45:42 PM 6/16/2008 1:45:42 PM...
À partir de l’écran « VOLTAGE », utiliser les touches de défilement ( , ) pour sélectionner les paramètres désirés et appuyer sur la touche d’entrée ( ) pour confirmer le paramètre. 200803004 93-2793 SU80k manual 4C.indd F126 200803004 93-2793 SU80k manual 4C.indd F126 6/16/2008 1:45:42 PM 6/16/2008 1:45:42 PM...
( • Utiliser les touches de défilement ( ) et la touche d’entrée ) pour sélectionner un des choix du menu. 200803004 93-2793 SU80k manual 4C.indd F127 200803004 93-2793 SU80k manual 4C.indd F127 6/16/2008 1:45:42 PM 6/16/2008 1:45:42 PM...
Remarque: si deux onduleurs sont utilisés dans une configuration de redondance parallèle, les numéros d’identification des onduleurs parallèles doivent être 1 et 2. 200803004 93-2793 SU80k manual 4C.indd F129 200803004 93-2793 SU80k manual 4C.indd F129 6/16/2008 1:45:42 PM 6/16/2008 1:45:42 PM...
Utiliser les touches de défilement ( , ) et la touche d’entrée ( ) pour sélectionner un des choix du menu. 200803004 93-2793 SU80k manual 4C.indd F130 200803004 93-2793 SU80k manual 4C.indd F130 6/16/2008 1:45:43 PM 6/16/2008 1:45:43 PM...
Vous devez saisir le mot de passe administrateur pour confirmer la remise à zéro. Remarque : Appuyer sur la touche « ESC » pour retourner au menu précédent. 200803004 93-2793 SU80k manual 4C.indd F131 200803004 93-2793 SU80k manual 4C.indd F131 6/16/2008 1:45:43 PM 6/16/2008 1:45:43 PM...
Vous devez saisir le mot de passe administrateur pour confirmer la remise à zéro. Remarque : Appuyer sur la touche « ESC » pour retourner au menu précédent. 200803004 93-2793 SU80k manual 4C.indd F132 200803004 93-2793 SU80k manual 4C.indd F132 6/16/2008 1:45:43 PM 6/16/2008 1:45:43 PM...
Défaillance du commutateur statique de dérivation Le commutateur de transfert statique de dérivation est anormal. Remarque : Si vous désirez que les messages facultatifs soient activés, communiquer avec Tripp Lite. 200803004 93-2793 SU80k manual 4C.indd F137 200803004 93-2793 SU80k manual 4C.indd F137 6/16/2008 1:45:44 PM...
L’onduleur possède six connexions de sortie à contact sec. Ces contacts peuvent être normalement ouverts ou fermés. INTERFACE DE SORTIE Á CONTACT SEC 200803004 93-2793 SU80k manual 4C.indd F138 200803004 93-2793 SU80k manual 4C.indd F138 6/16/2008 1:45:44 PM 6/16/2008 1:45:44 PM...
Utiliser uniquement le câble parallèle de redondance inclus avec l’onduleur. Tenter de relier les onduleurs avec un câble incompatible endommagera les onduleurs et provoquera un risque sérieux de blessure et de dommages à la propriété. 200803004 93-2793 SU80k manual 4C.indd F139 200803004 93-2793 SU80k manual 4C.indd F139...
équipement. Tripp Lite a instauré une politique d’amélioration continue. Les spécifications sont sujettes à changement sans préavis. Fabriqué en Chine. 200803004 93-2793 SU80k manual 4C.indd F141 200803004 93-2793 SU80k manual 4C.indd F141 6/16/2008 1:45:44 PM 6/16/2008 1:45:44 PM...