3. Protocol Application
Inputs Status
Address
10201
10202
10203
10204
10205
10206
UPS Power Integration Fault Alarm
10207
Note: the status what value is 1 is effective
3.3 Output Registers (Address: 2XXXX) Data Content
Output Registers
Address
20001
20002
20003
20010
Resume Pretermission
20020
Table 3.2.3 Node Status Information
Content
Mains Abnormal
Battery Under Voltage
Bypass Output
UPS Fault
Invert Output
Over Temperature
Table 3.3.1 Control Command
Content
Size
Inverter On
2 Bytes
Inverter Off
2 Bytes
Battery Test
2 Bytes
Battery Resist Test
2 Bytes
2 Bytes
Rating Parameter
Type
Definition
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Range
Unit
If this address is written, the UPS will
Second
turn inverter on; the data is the value of
If this address is written, the UPS will
Second
turn inverter off; the data is the value of
If this address is written, the UPS will
perform battery test; the data is the value
Second
of test time. If the value is 0, the test will
If this address is written, the UPS will
test battery resist; the data can be any
If this address is written, the UPS will
resume pretermission rating parameter;
the data can be any numerical value.
25
Remark
Remark
delay time.
delay time.
stop.
numerical value.