Burner Start-Up Cycle - Riello 40 F5 Instrucciones Para La Instalación, Uso Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4
AIR DAMPER ADJUSTMENT
The values stated in the table are necessary for the first setting of air-damper.
They are relevant to a burner with mounted cowling and combustion chamber with depression zero.
These values can be adjusted, if necessary, till reaching 1 bacharach.
ELECTRODE ADJUSTMENTS
Attention:
Before assembling or removing
the nozzle, loosen the screw (B)
and move the electrodes ahead.

BURNER START-UP CYCLE

Normal
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
WARNINGS TO AVOID BURNOUT OR BAD COMBUSTION OF THE BURNER
– When the burner is stopped, the smoke pipe must be opened and effect a natural draught in
the combustion chamber. If the smoke pipe is closed, the burner must be drawn back till the
extraction of blast tube from the furnace. Before operating in this way take the voltage off.
– The place, where the burner works, must have same openings suitable for the passage of air
necessary for combustion. To be sure about this, you have to control the smoke number of
exhaust gas with all the windows and doors closed.
– If in the place, where the burner works, there are air-breathings, check the existence of air-
input openings with dimensions suitable for the necessary air-exchange. In any case check
that, when the burner is stopped, the air-breathings do not draw warm smokes from pipes
through the burner.
2093
D5288
~
12s
Only for code 3451082 - 3451084
MOVE THE ELECTRODE HOLDER
BACKWARDS TO THE END
4 ±
0.3 mm
B
Lock-out, due to light-failure
~
6
GB
2.5 ±
~
12s
5s
0.3 mm
D5229

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

462m345108234510843451085

Tabla de contenido