MODEL: 190102000010
INSTALLATION
ATS systems are designed for when there is a drop or
loss of incoming mains power, ATS panels are designed
to automatically start and stop a generator for emergency
backup power supply.
When mains power supply is low or lost the generator
will start in within 6 seconds and then supply power to
consumer unit or switch. When mains incoming power
supply returns the ATS panel will automatically transfer
back to incoming mains power supply and then stop the
generator within approx. 15 seconds.
This system uses SCM core and digital technics to control and
manage the automatic working system.
EASY INSTALLATION AND OPERATION
Automatic working with no maintenance required. If transfer
panel has a fault it will register a solid RED fault light on the
panel and indicate user/engineer to inspect and re-set. Don't
worry about incoming mains supply and generator power supply
LED on at the same time this is normal when changing over.
There is a battery charger inside the ATS panel, this will ensure
when your generator isn't running that the battery will charge
thoroughly.
OPERATION
Use the ATS input cable (Supplied) to connect the ATS panel
to the generator control panel. Turn the ignition switch
on the front panel of the generator to the 'OFF' position
for diesel generators and the 'ON' position for petrol
generators.
AUTOMATIC POSITION SETUP
Press AUTO button, the solid GREEN indicator LED will illumi-
nate, ATS system is now set and in automatic mode.
ATS SYSTEM WORKING
When in AUTO mode, if there is drop or loss in incoming mains
power the ATS system will automatically open air damper con-
trol and start the generator in approx. 3 seconds. The generator
will run for 5-6 seconds and then apply load to the ATS panel
and then the consumer unit.
THE ATS PANEL WILL ATTEMPT TO START THE
GENERATOR 3 TIMES
If generator cannot start successfully within 3 attempts
the solid RED indicator light will illuminate. You will need to
inspect the reason why it hasn't started and reset the ATS
panel to remove the illuminated 'RED' fault light by pressing
the Auto/Manual button once.
GENERATOR START/STOP
When mains power supply is lost, the generator will attempt to
start within 5 seconds.
If unsuccessful, the generator will wait a further 5 seconds
before attempting to start again. If after 3 attempts, it still
cannot start, the 'RED' fault light will illuminate.
If the generator fails to start and the 'RED' fault light is
illuminated then there could be an issue with generator or
ATS panel and it needs to be investigated
COMMON FAULTS:
– Auto/Manual button wrong position
– ATS communication lead unplugged
– Ignition key wrong position
– Generator battery low or dead
– RUN lever wrong position
– Fuel supply issue
If all the above have been checked first then an experienced
engineer needs to attend to investigate or call repair centre
immediately.
When mains power supply returns, ATS panel will transfer
load to incoming mains supply and generator will stop running
approx. 15 seconds later.
Manual Start
In the event of a panel failure you can use the manual lever
override inside the ATS panel.
High voltage. A qualified electrician should only be used.
Always Isolate the incoming power supply before opening
the panel door.
If you don't need the ATS panel to work automatically you can
use the manual feature by pressing the 'Auto/Manual' button on
the front of the panel.
2
INSTALLATION
WARNING
NOTICE
WARNING