MODEL: 190102000010
Manual Start
– Switch: Controls internal wiring power. If switch is turned
to the position 'I' ATS panel is turned 'ON' and will start
generator automatically if incoming power drops or is lost. If
switch is in the position '0' ATS panel is turned OFF and no
power from either incoming or generator.
– Manual mode: Turn safety key (Supplied) first to manual
position on switch and then turn handle to 'II' to activate
manual generator supply mode. WARNING Whilst in manual
mode you DO NOT try use auto mode without first turning
the safety key back to auto position.
– Manual handle: Before using manual handle, WARNING
mains power supply needs to be isolated and turned 'OFF'.
DO NOT try to change switch from auto to manual without
first isolating incoming supply.
– Padlock: Maintenance only. Turn the switch & handle to
position "0" then lift up the padlock. When the padlock is
in place the internal handle is isolated, switch and manual
handle will now not work.
AUTOMATIC AIR DAMPER CONTROL
If generator have air damper control to start, ATS panel will
automatically open and close it before generator starts and
stops.
Battery maintenance
ATS panel will charge the battery automatically, charging
current is 2A.
Original family use power supply system:
1. Mains power
2. Air Switch
3. Switch
4. Switch
5. Lightin
6. Lightin
7. Socket
8. Socket
9. Socket
With ATS system:
1. ATS system
2. City power
3. Input
4. Power
5. Output
6. Generator
7. Input
8. Connect the main power of generator set
9. Generator control panel
10. Generator
11. Joint for connecting generator control panel
ATS SWITCH
When handle & switch is turned to position '0' it will turn off
both city power and standby power.
Operation indicator shows the electric power state.
"I" Incoming Supply,
"0" is Double power OFF and isolated,
"II" is Generator supply.
When mains power supply is lost, the generator will attempt
to start within 5 seconds.
If unsuccessful, the generator will wait a further 5 seconds
before attempting to start again. If after 3 attempts, it still
cannot start, the 'RED' fault light will illuminate.
3
ATS SWITCH
WARNING
EN