MODEL: 190102000010
1. Input power
2. Operation Indicator
3. Key Switch
4. Padlock
5. Output power
1. Handle
ATS MODE
– ATS power must be equal or smaller than the incoming main
supply.
– AIR-BREAKER can be installed to protect ATS system when
connecting mains power cable to ATS panel.
– Generator ignition key MUST be in the 'OFF' position on the
generator front panel to enable the generator to AUTO stop
& start. Note: If the ignition key is in the wrong position
generator will start but not auto stop.
– Before using the ATS panel in automatic mode you should
run the generator with the ATS panel unplugged.
– Run the generator with the ATS in the "Manual" position
first (Auto/Manual Button), stop generator and then you can
choose "AUTO" to test if working automatically.
– Turn air-breaker switch to "ON" position when ATS system
is in use. (If installed)
– Only qualified electrician can open panel for inspection and
repair, DANGER High Voltage
– Press 'AUTO' button on the front panel, Mains incoming
supply should be Illuminated
WIRING DIAGRAM 415V 3 PHASE
N: Neutral Wire
1: Input City Power
2: Generator Standby Power
3: Output Power
4: Padlock
ATS Port Configuration
1. 12v Power +
2. 12v Power -
3. Start Relay
4. Fuel Oil
5. (& 6) Judge frequency of flywheel