Ecoflam MAX GAS 350 PAB Manual Del Usuario página 22

Ocultar thumbs Ver también para MAX GAS 350 PAB:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 70
EN
Start up
­ Air pressure switch adjustment ­ Setting gas pressostat
Air pressure switch calibration
The air pressure switch is provided for
monitoring the pressure of the
combustion air fan.
Unscrew screws A and B and remove
cover C. After the air and gas setting you
have to calibrate the air switch with the
burner working on the low flame by slowly
turning the relative knob clockwise until the
burner locks out. Read the value and then
decrease it by 15%.
Min gas pressure switch
The gas pressure switch has the function
to check that the gas pressure before the
gas valve does have the minimum
pressure to make the burner running
correctly.
Unscrew off and remove cover M.
- Set knob N to a value equal to 60% of
gas nominal feed pressure (i.e. for natural
gas nom. pressure = 20 mbar, set knob to
a value of 12 mbar; for LPG nom. pressure
of G30/G31- 30/37 mbar, set knob to a
value of 18 mbar). Screw up cover M.
Operating check
Flame monitoring must be checked
for safety as part of initial
WARNING
commissioning and also after
Test
Date
Model
Type gas
Gas calorific value
Gas inlet pressure
Adjustment gas pressure
Volumetric gas flow rate
Burner output
Burner output
Flue gas temperature
Air temperature
CO
2
CO
NOx
Performance
Corrective action
Operator name
Company
22
www.ecoflam­burners.com
WARNING: the air pressure switch
shall prevent the air pressure to go
below 85% from the adjustment
WARNING
value in order to prevent the CO in the
fumes to exceed 1% (10000 ppm).
servicing or if the system has been out of
operation for any significant period of time.
- Start attempt with gas ball valve closed:
the automatic combustion control unit must
Recording commissioning data
WARNING
n°1
mbar
Nm
3
/h
min
kW
max
kW
%
ppm
ppm
%
C
A
B
M
I
L
switch to gas shortage or malfunction after
the end of the safety period.
n°2
n°3
420010489905
D
N
n°4