Holding registers (Read and write)
Register Discrete input
40001
Addressing
40002
Baud Rate
40003
Parity
40011
SetPoint HR
40012
SetPoint VOC/CO2
Relay SetPoint
40013
Hysteresis HR
Relay SetPoint
40014
Hysteresis VOC/CO2
40015
Light guide intensity
Temp Measurement
40021
Tuning
VOC/CO2
40022
Measurement Tuning
HR Measurement
40023
Tuning
Green LED
40024
illumination stop HR
Red LED
40025
illumination start HR
Green LED
40026
illumination stop
VOC/CO2
Red LED illumination
40027
start VOC/CO2
Data type
Range
16bits
1-247
48 : 4800
96 : 9600
16bits
192 : 19200
384 : 38400
0 : EVEN
16bits
1 : ODD
2 : Non parity
16bits
60-100
16bits
800-2000
16bits
0-20
16bits
0-500
16bits
0-100
16bits
-30-30
16bits
-200-200
16bits
-10-10
16bits
0-60
16bits
80-100
16bits
400-800
16bits
800-2000
Default Comments
1
Channel
192
Bus speed
0
Parity
Set Point for HR version
70
(%) MF4 mode
Set Point for VOC and
1200
CO2 versions (ppm) MF4
mode
Relay hysteresis for HR
5
set point (%)
Relay hysteresis for VOC
200
and CO2 set point (ppm)
Led diffusor intensity (%)
80
MF4 mode
Temperature reading
0
adjustment (°C)
VOC and CO2 reading
0
adjustment (ppm)
HR reading adjustment
0
(%)
Green LED end for HR
60
version (%)
Red LED start for HR
80
version (%)
Green LED end for VOC/
800
CO2 version (%)
Red LED start for VOC/
1200
CO2 version (%)