DEHUMIDIFIER SET UP
3
1. Important Precautions
•
If used near a water source, be certain that there is no chance the unit could get splashed. Connecting the
unit to a dedicated circuit with Ground Fault Circuit Protection (GFCI) is recommended. Electrical wires must
be properly grounded, and with the capability to be disconnected to provide for service.
•
The device is designed to be installed indoors in a space that is protected from rain and flooding.
•
Tamper proof fasteners provide access to the front of the device for operation, maintenance and service.
•
Avoid directing discharge air at occupants.
•
DO NOT place sides, top or bottom of cabinet in direct contact with structural building members or
unwanted noise may result. Unit is designed to be suspended by side mounting flanges only.
•
Drain hose must be routed with downward slope from unit drain connection to appropriate location. Consult
local building codes for acceptable condensate drain connections.
2. Location Considerations
•
Install the unit on or inside of an interior wall and with direct connection to building electrical service.
A 15 Amp circuit must be provided. Install the unit in a location that is near a power supply.
•
Electrical and plumbing rough-in must be provided to installation location, adhering to any applicable local
codes.
•
Install the unit in a central location to maximize air circulation and efficiency. Do not locate inside a closet
or mechanical room with the diffuser cover facing inward where both supply and return air will be limited.
•
Install the unit such that discharge air is directed away from thermostats and not installed inside of a wall
cavity that contains a thermostat.
•
The unit generates condensate. Install the unit with nearby access to a drain or determine if there will be a
need for a condensate pump.
•
The unit will fit within 16" O.C. stud walls. If walls are more or less than 16", consideration must be given to
providing additional support.
•
Rough opening must be a minimum of 2" off the floor, 6" from the ceiling, and 10" from an inside corner.
•
Check that there are no hidden wires or pipes inside the wall where unit is to be installed. Contact a certified
electrician or plumber before removing any wires or pipes inside the wall.
800.533.7533 | Santa-Fe-Products.com
Santa Fe ULTRAMD33 Installation & Operation Instructions
5