DRAIN INSTALLATION CONSIDERATIONS
4
Consult local building codes for condensate drain restriction and additional requirements. The Santa Fe
UltraMD33 is provided with 10' of 3/4" I.D. drain hose. Verify drain hose length is appropriate for application.
The hose must be connected to the drain port and routed down the wall cavity and into the air conditioning
condensate drain or other acceptable drainage.
•
For gravity drainage, the bottom of the unit must be at, or above the drain height.
•
Avoid any entrapment of stagnant water within the hose.
•
Consider 1/4" drop for every foot of drain hose.
•
Codes may dictate that a drain trap is necessary before or near to the main building drain.
Be sure to install the metal cover over the top of the hose. This prevents air from entering the unit through the
wall cavity.
ELECTRICAL REQUIREMENTS
5
A 10' long power cord is included for installations where a plug-in connection is permitted in accordance with
the National Electrical Code and local codes and ordinances. A dedicated 15A circuit and GFCI receptacle are
recommended. Electrical connections inside the device are made with the included wire nuts. Route the cord
through the appropriate knockout and secure with the non-metallic cable clamp.
If not using the included 10' power cord,
ensure that the electrical connection and
wire size are adequate and in conformance
with the National Electrical Code,
ANSI/NFPA 70 – latest edition and all local
codes and ordinances. Use flexible,
armored, or non-metallic sheathed, copper
wire with grounding conductor. Use the
included non-metallic cable clamp as required.
•
The Santa Fe UltraMD33 requires 120-volt,
60 Hz, AC-only, 15 amp, fused and
grounded electrical supply.
•
A visible circuit breaker or disconnect
switch near the unit is required for
maintenance and service.
•
A dedicated circuit is recommended.
•
Use of a UL listed or CSA approved
strain relief is required.
6
Santa Fe ULTRAMD33 Installation & Operation Instructions
Wiring Schematic
Santa-Fe-Products.com | 800.533.7533