It allows you to enter the access protection code to control panel programming.
You can enter an alphanumerical code of four characters using the numbers from 0 to 9 and the letters A-B-C-D-E-F.
The default value is 0000 (four zeros) and indicates the absence of the protection code.
At any time, you can cancel the code entering operation, pressing the + and - keys simultaneously. Once the password is entered,
you can operate the control panel, entering and exiting programming for a time of approx. 10 minutes, to allow the adjustment and
test operations of the functions.
By replacing the code 0000 with any other code, you enable protection of the control panel, preventing access to all the menus.
If you want to enter a protection code, proceed as follows:
- select the Code menu and press OK.
- the code 0000 is displayed, even if a protection code has already been previously entered.
- use the + and - keys to change the value of the flashing character.
- the OK key confirms the flashing character and moves on to the next one.
- after entering the 4 characters, a "CONF" confirmation message appears.
- after a few seconds, the code 0000 is displayed again.
- it is necessary to reconfirm the previously entered protection code in order to avoid unintentional entries.
If the code corresponds to the previous one, an "OK" confirmation message is displayed.
The control panel automatically exits the programming phase and to access the menu again, the saved protection code will be neces-
sary.
IMPORTANT: NOTE the protection code and KEEP IT IN A SAFE PLACE for future maintenance. To remove a code from a
protected control panel, you should enter programming with the password and bring the code to the default value 0000.
IF THE CODE IS LOST, IT IS NECESSARY TO CONTACT THE AUTHORISED TECHNICAL
SERVICE CENTRE FOR A TOTAL RESET OF THE CONTROL PANEL.
If you have a transmitter already stored in the receiver, it is possible to carry out radio remote learning (without having to access the
control panel).
IMPORTANT: The procedure must be carried out with the gate in opening during the TCA pause or the gate open if the TCA
logic is OFF. The REM logic must be ON.
Proceed as follows:
1 Press the hidden key of the transmitter already stored.
2 Press, within 5s, the key of the transmitter already stored corresponding to the channel to associate with the new transmitter. The
flashing light comes on.
3 Press, within 10s, the hidden key of the new transmitter.
4 Press, within 5s, the key of the new transmitter to associate with the channel chosen in point 2. The flashing light goes out.
5 The receiver memorises the new transmitter and immediately exits programming.
F1: T4A - Main safety fuse.
F2: Resettable safety fuse for accessories power supply output.
Intervenes in the event of overload or short circuit on 24 Vdc output. In this case, disconnect the control panel and check the connec-
tions or the quantity of accessories connected to the 24Vdc output. Once the connections are reset in correct mode, the accessories
power supply output will automatically start working again.
The CP.SAM control panel includes the power supply board prepared for connection in series of two batteries 12V 2,1Ah DA.BT2
(optional) which enable operation of the automation also in the event of temporary absence of the mains power supply.
During normal operation of the mains, the CP.SAM board recharges the batteries.
The maximum load current is 1A, the average loading current is 300mA. (respect polarity). For installation of the batteries, consult the
instructions supplied with the SM.CB kit.
SWO1
SWO2
SWC1
SWC2
P.P.
PED
OPEN
PHOT
STOP
PHOT-C
DAS
34
PASSWORD (CODE)
TRANSMITTERS REMOTE LEARNING
FUSES AND GUARDS
EMERGENCY BATTERY
On each input, a display segment is associated which in the event of activation switches
on, according to the following board.
CLOSE
The N.C. inputs are represented by the vertical segments.
The N.O. outputs are represented by the vertical segments.
The control panel displays the message AMP 1 or AMP2 in the event of intervention of the
anti-crushing device amperometric sensor.
DIAGNOSTICS