Function Of Automatic Wiring/Piping Correction - mundoclima H11 Serie Manual De Instalación Y Usuario

Ocultar thumbs Ver también para H11 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

6. Function of automatic wiring/piping correction

Automatic Wiring/Piping Correction Function:
More recent models now feature automatic correction of wiring/piping errors. Press the "check
switch" on the outdoor unit PCB board for 5 seconds until the LED displays "CE", indicating that this
function is working, Approximately 5-10 minutes after the switch is pressed, the "CE" disappears,
meaning that the wiring/piping error is corrected and all wiring/piping is properly connected.
How To Activate This Function:
1. Check that outside temperature is above 5℃ .
(This function does not work when outside temperature is not above 5℃ )
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Turn on the breaker and wait at least 2 minutes.
4. Press the check switch on the outdoor PCB board unit LED display "CE".
Correct wiring
Terminal
block
Liquid/
Gas pipe
Outdoor unit
Incorrect wiring
Terminal
block
Liquid/
Gas pipe
Outdoor unit
Incorrect wiring
Terminal
block
Liquid/
Gas pipe
Outdoor unit
Check switch
B
A
Indoor unit B
B
A
Indoor unit A
B
A
Indoor unit B
B
A
Indoor unit A
B
A
Indoor unit B
B
A
Indoor unit A
41
LED display

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido