Water Piping - mundoclima AEROTHERM MAM-V9 Serie Manual De Usuario E Instalacion

Monobloc
Ocultar thumbs Ver también para AEROTHERM MAM-V9 Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

9.4 Water piping

All piping lengths and distances have been taken into consideration.
The maximum allowed thermistor cable length is 20m. This is the maximum
allowable distance between the domestic hot water tank and the unit (only for
installations with a domestic hot water tank).The thermistor cable supplied with
the domestic hot water tank is 10m in length.In order to optimize efficiency we
recommend installing the 3-way valve and the domestic hot water tank as close
as possible to the unit.
If the installation is equipped with a domestic hot water tank (field supply), please refer to the domestic hot water tank
Installation And Owner's Manual. If there is no glycol (anti-freeze) in the system there is a power supply or pump failure,
drain the system (as shown in the figure below).
If water is not removed from the system in freezing weather when unit is not used. The frozen water may damage the
water circle parts.
9.4.1 Check the water circuit
The units are equipped with a water inlet and outlet for connection to a water circuit.
The units should only be connected to closed water circuits. Connection to an open water circuit would lead to excessive
corrosion of the water piping. Only materials complying with all applicable legislation should be used.
Example:
1
1.6
1.7
1.5
1.8
1.3
1.4 1.2
Requirements
NOTE
NOTE
1.1
2
3
6
7
8
124
Thermistor cable length minus 2m
4
9
8.1
10
8.2
FHL1
FHL2
Valve
11
17
----
----
FHLn

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido