4
DEHUMIDIFIER SET UP
2. Location Considerations
•
Allow sufficient clearance to handle the unit's overall dimensions as well as the necessary return and
supply ductwork to the unit.
•
Allow sufficient clearance for filter removal and to prevent airflow obstruction.
•
Electrical service access will require the removal of the outside shell. Allow sufficient clearance around the
unit.
•
Locate the dehumidifier in an area where the unit's 9 ft. cord can easily reach electrical outlet.
•
Locate the dehumidifier in an area where field wiring the control (low voltage) to the unit will be possible.
•
A back draft damper is required in the supply duct of the Santa Fe Ultra70, especially when connecting to
the supply ducting system. The backdraft damper prevents supply air from counter flowing through the
Santa Fe Ultra70 when it is not operating. The dehumidifier's location should be chosen to allow installation
of this accessory if necessary.
•
The Santa Fe Ultra70 may be suspended with the hang kit or a suitable alternative from structural members,
ensuring the assembly supports the dehumidifier's base in its entirety. Do not hang the Santa Fe Ultra70
from its' cabinet.
•
Allow for proper drainage and routing of needed drain pipes.
MINIMUM
CLEARANCE
FOR FILTER
(EITHER SIDE)
6
Santa Fe ULTRA70 Installation & Operation Instructions
6" MINIMUM CLEARANCE
FOR PROPER AIR FLOW
A
DRAIN
ACCESS
13"
FILTER
ELECTRICAL SERVICE
ACCESS THIS SIDE
TOP VIEW
9' POWER CORD
A
RETURN AIR DUCT
B
SUPPLY AIR DUCT
B
Santa-Fe-Products.com | 800.533.7533