en
6 Operation
Tab.37
For user
Parameters
ROOM CARD
CLEAN FILTER TIME
TEMP UNIT
DISPLAY ROOM TEMP
ROOM SENSOR SEL
HEAT AMEND
COOL AMEND
SET MIN COOL
SET MAX HEAT
COOL OVER TEMP FAN
Tab.38
For machine
Parameters
IDU ADDR
GROUP ADDR
LINECTRL ADDE
IDU TYPE
IDU CAPACITY
FAN SET
MOTOR MODE
RUN TYPE
MOTOR TYPE
56
Description
Set the room card.
Can be set from 0 to 3.
Set the clean filter period.
When the set period is reached, the
pops up on the home screen.
Set time = set value x 500h.
Can be set from 1 to 255.
Set the temperature unit.
0: Centigrade
1: Fahrenheit
Set the display room temperature
0: no display of room temperature
1: display of room temperature
Set the temperature transmission
0: return air temperature transmission
1: wired controller temperature transmission
2: refrigeration return air temperature transmission, hot
wired controller temperature transmission
Ring temperature sensor for temperature compensation, ad­
just the unit to reach the temperature stop temperature.
Can be set from 21 to 29.
Ring temperature sensor for temperature compensation, ad­
just the unit to reach the temperature stop temperature.
Can be set from 21 to 29.
Set the lower limit of cooling temperature
Can be set from 16 to 32.
Set the upper limit of heating temperature.
Can be set from 16 to 32.
Set the cool over temperature fan.
0: run according to the set wind speed
1: stop the fan
Description
Internal communication address
Internal centralized control address
Address of internal machine wired controller
Indoor unit type
Indoor unit capacity
Wind speed/static pressure selection
External drive fan working mode
Model operation mode selection
Motor type
2. Select FOR SERVICEMAN and press MENU/OK.
3. Input the correct password and press MENU/OK to enter the service
page.
4. Select SET PARAMETER and press MENU/OK.
5. Set, if needed, the following parameters.
Parameters in the FOR USER menu can be adapted to the needs of the
end user.
filter cleaning icon
icon on home screen.
C
IN
Parameters in the FOR MACHINE menu are factory set according to the
air conditioner model.
Factory Settings
0
5: 2500h
0: Centigrade
0: no display of room temper­
ature
Factory set according to the
air conditioner model.
25°C
25°C
16°C
32°C
0: run according to the set
wind speed
7802133 - v01 - 21072022