SIMIREL
Time relay for plug-in socket
Operating Instructions
!
WARNING
HAZARDOUS VOLTAGE.
Can cause electrical shock
and burns.
Disconnect power before proceeding
with any work on this equipment.
Reliable functioning of the equipment is only ensured with
certified components.
General description
•Functions: A, b, C, d, di, H
•11 timing ranges: 99.99 s; 999.9 s; 9999 s; 99 min 59 s;
99.99 min; 999.9 min; 9999 min; 99 h 59 min; 99.99 h;
999.9 h; 9999 h
(Note: the 99.99 s range is inhibited for the d and di intermit-
tent modes)
•Simultaneous and constant display of the current value and
pre-selection value (internal battery, minimum life span 10
years at 20 °C)
•Up count (Up) or down count (Down) display
•Contact input
•8 A/250 V AC relay output (10 A UL)
•Power supply: 24 V AC/DC / 110 V AC bis 240 V AC (tole-
rance +10 % - 15 %)
•Front panel protection rating IP65
Readout legends (see fig. I)
1 Power supply symbol
2 Closed control contact symbol
3 Flashing symbol during time delay
4 Current value readout (4 digits)
5 Unit of time
6 Setting the decimo separator
7 Operating modes
8 Increasing (Up) or decreasing (Down) mode
9 Time range
10 Changeover relay status symbol
(NC = Normally Closed, NO = Normally Opened)
11 Next stage
12 Configuration validation
13 Incrementation of time T
14 Display of time pre-selection T (4 digits)
2
Order No.: 7ZX1012-0PV34-1AA1
Operating modes (see Fig. III for function diagrams)
Function A: ON-delay
Function b: Pulse-shaping
Function C: OFF-delay
Function H: Passing make contact
Function d: Flasher; repeat cycle; starting with interval
Function di: Flasher; repeat cycle; starting with pulse
Programming (see fig. IV)
•To program, simply set the switch on the side of the unit to
the ON position.
•If the timer has started running, the time delay values:
- are taken into account immediately if your display is on the
up count (Up) and if the new value is greater than the time
that has already elapsed,
- will be taken into account in the next cycle if you are on a
down count display (down)
•The unit is supplied with the following configuration: 01.00 s,
d (down), C (mode), Prog = ON
•If, inadvertently, you enter the unit test procedure with the
entire screen or certain segments of the screen flashing,
press the MODE push-button until Bp is obtained on the
screen, then press VALID to return to normal operation.
•Incrementation of value T by pressing one of the 4 keys Ë
corresponding to each digit.
Utilization precautions
•The power cables and input circuits must be separate.
•A minimum requirement for ventilation and protection from
vibration must be provided.
ATTENTION
This equipment contains a lithium battery, do not
incinerate the unit.
Dimensions and assembly (see fig. V)
A Panel cut out
15 Seal
16 Positioning screw
17 Frame for panel-mounting
18 Panel thickness 1 to 3.5 mm
Wiring-Diagram (see fig. II and VI)
Accessories
•11 pole plug-in socket for standard mounting rail
LZX: MT78750
•11 pole plug-in socket with rear connection 7PX9921
7PV3
DIN VDE 0660, IEC 60947
English