Connections must be made with cables of an appropriate cross-section.
Function
Mains input
Ground (FUNCTIONAL,
NOT FOR PROTECTION)
Battery
48V Output
Alarms
7.1
CONNECTION OF THE MAINS POWER:
This connection is made with a BLZP 5.08HC/02/180F (WEIDMÜLLER) plug-in connector, with 5.08mm pitch
or equivalent (2-pole).
The connection is made on the side of the device (under the model label), next to where "Neutral" and "Phase"
are printed on the device.
It must be ensured that the mains power is de-energized before the device is connected. The device must not
be connected to any mains power that does not have a rated voltage of 230Vac 50Hz.
Phase and neutral can be connected interchangeably.
7.2
GROUND, OUTPUT AND BATTERY CONNECTION:
The connection will be made with a BLZP 5.08HC/06/180F (WEIDMÜLLER) plug-in connector, with 5.08mm
pitch or equivalent (6-pole).
The connection is made on the side, opposite the model label, and the connector detail can be seen in the
following figure:
www.premiumpsu.com
Powering Your Challenge
Connection
1-Phase, 2-Neutral
1-Ground
3-Battery +, 4-Battery -
5-48V-, 6-48V+
1-URG, 2-FAU, 3-FAC, 4-NUR, 5-COM
Figure 17. AC Connections
Manual de Operación
Minimum
recommended
permissible copper
copper cross-
cross-section
section
0.75 mm
2
1 mm
2
1 mm
2
1 mm
2
0.25 mm
2
Serie EPS
Maximum
2.5 mm
2
2.5 mm
2
2.5 mm
2
2.5 mm
2
1.5 mm
2
MA-5192A-1
20-10-2021
21 / 84