Function 06 Write Single Register & Function 16 Write Multiple Register & Function 03 Read Multiple Holding Registers
Register
Variable description
4x0001
Physical parameter displayed
Standard display (cyclic):
VOC in %, CO2 in ppm, temperature in °C,
relative humidity in % r.H., particulate matter
(PM) in μg/m3
Display fi xed to CO2 in ppm
Display fi xed to VOC in %
Display fi xed to Temperature
Display fi xed to Relative humidity in % r.H.
Display fi xed to Particulate matter (PM) in μg/m -
Freely confi gurable display – 10
4x0002
RESERVED
4x0003
RESERVED
4x0004
RESERVED
4x0005
RESERVED
4x0006
RESERVED
4x0007
RESERVED
4x0008
RESERVED
4x0009
RESERVED
4x0010
RESERVED
4x0011
RESERVED
4x0012
RESERVED
4x0020
Brightness LCD-backlighting
4x0021
RESERVED
4x0022
RESERVED
4x0023
Off set Temperature
4x0024
Off set Humidity
Function 08 Diagnostics
Sub Function Code
00
01
04
10
11
12
13
14
15
Function 17 Report Slave ID
Sub Function Code
00
01
02
03
04
05
06
20
Data Type
Unsigned 8 bit
-
-
-
-
-
-
Unsigned 8 Bit
Signed 10 Bit
Signed 10 Bit
Parâmetro
Echo of transmission data (Loopback)
Restart Modbus (Reset listen-only mode)
Activation listen-only mode
Delete counter
Counter bus telegrams
ter communication errors (Parity, CRC, frame errors, etc.)
Counter exception messages
Counter slave messages
Counter messages without answer
Parâmetro
Number of bytes
Slave ID (device type)
Slave ID (device class)
03 Status
04 Version number (release)
05 Version number (version)
06 Version number (index)
Predefi -
Mín.
Max.
Saved
value
nição
Value
value
0
SIM
0
10
-
-
0
0
-
-
1
1
-
-
2
2
-
-
3
3
-
-
4
4
-
-
6
6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
100
SIM
0
63
-
-
-
-
0
SIM
-100
100
0
SIM
-100
100
Data Type
ANSWER
Echo data
Echo message
No answer
Echo telegram
Unsigned 16 bit
All valid bus messages
Unsigned 16 bit
Faulty bus messages
Unsigned 16 bit
Error counter
Unsigned 16 bit
Slave messages
Unsigned 16 bit
Broadcast messages (address 0)
Data Type
ANSWER
Unsigned 8 bit
6
Unsigned 8 bit
AERSGARD® MODBUS
19 = T,H,C
20 = T,H
T: temperature
H: relative humidity
C: carbon dioxide (CO2)
Unsigned 8 bit
60 = AERASGARD® / AERASREG®
Unsigned 8 bit
255 = RUN, 0 = STOP
Unsigned 8 bit
1....9
Unsigned 8 bit
1...99
Unsigned 8 bit
1
Sonde DP +030220662 rel. 2.4 - 27.09.2022
Min.
Max. range
range
0
10
Def.
Def. Settings
Settings
1
1
2
2
3
3
4
4
6
6
0
100 %
-10 K
+10 K
-10 %
+10 %
Tab. 3.g

Publicidad