Tabela de variáveis do produto montado no ducto
Function 04 Read Input Register
Register
Variable description
3x0001
CO2 Value Sampling 4s
3x0002
CO2 Value Sampling 32s
3x0003
RESERVED
3x0004
RESERVED
3x0005
Temperature Value Sampling 4s
3x0006
Temperature Value Sampling 32s
3x0007
Relative humidity Value Sampling 4s
3x0008
Relative humidity Value Sampling 32s
Function 05 Write Single Coil & Function 01 Read Coils
Register
Variable description
0x0001
Reset (Auto zero) CO2
0x0002
RESERVED
0x0003
Automatic calibrationCO2
0x0004
RESERVED
0x0005
RESERVED
0x0006
RESERVED
0x0007
RESERVED
0x0008
RESERVED
0x0009
temperature measurement type
Function 06 Write Single Register & Function 16 Write Multiple Register & Function 03 Read Multiple Holding Registers
Register
Variable description
4x0023
Off set Temperature
4x0024
Off set Humidity
Function 08 Diagnostics
Sub Function Code
00
01
04
10
11
12
13
14
15
Function 17 Report Slave ID
Sub Function Code
00
01
02
03
04
05
06
Sonde DP +030220662 rel. 2.4 - 27.09.2022
Parâmetro
Echo of transmission data (Loopback)
Restart Modbus (Reset listen-only mode)
Activation listen-only mode
Delete counter
Counter bus telegrams
Counter communication errors (Parity, CRC, frame errors, etc.) Unsigned 16 bit
Counter exception messages
Counter slave messages
Counter messages without answer
Parâmetro
Number of bytes
Slave ID (device type)
Slave ID (device class)
03 Status
04 Version number (release)
05 Version number (version)
06 Version number (index)
Predefi -
Saved
Data Type
value
nição
Signed 16 Bit
-
-
Signed 16 Bit
-
-
-
-
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Signed 16 Bit
-
-
Predefi -
Saved
Data Type
value
nição
Bit 0
0
NÃO
-
-
Bit 2
0
SIM
-
-
-
-
-
-
-
-
-
-
Bit 8
0
SIM
Predefi -
Saved
Data Type
value
nição
Signed 10 Bit
0
SIM
Signed 10 Bit
0
SIM
Data Type
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Unsigned 16 bit
Data Type
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Unsigned 8 bit
Mín.
Máx.
Mín.
Máx.
inter-
inter-
Value
value
valo
valo
350
5000
350
5000
350
5000
350
5000
-350
800
-35C
80C
-350
800
-35C
80C
0
1000
0
100 %
0
1000
0
100 %
Mín.
Máx.
Mín.
Máx.
inter-
inter-
Value
value
valo
valo
0
1
OFF
ON
0
1
OFF
ON
0
1
°C
°F
Mín.
Máx.
Mín.
Máx.
inter-
inter-
Value
value
valo
valo
-100
100
-10 K
+10 K
-100
100
-10 %
+10 %
ANSWER
Echo data
Echo message
No answer
Echo telegram
All valid bus messages
Faulty bus messages
Error counter
Slave messages
Broadcast messages (address 0)
ANSWER
6
AERSGARD® MODBUS
17 = T,H,V,P,C
18 = T,H,V,C
19 = T,H,C
20 = T,H
21 = T,H,P
T: temperature
H: relative humidity
V: air quality (VOC)
P: particulate matter (PM)
C: carbon dioxide (CO2)
60 = AERASGARD® / AERASREG®
255 = RUN, 0 = STOP
1....9
1...99
1
Tab. 3.h
POR
21