Descargar Imprimir esta página

ABB ACQ580-34 Instalación Rápida Y Guía De Introducción página 20

Ocultar thumbs Ver también para ACQ580-34:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 41
20 EN – Quick installation and start-up guide
Parameter
58.06 Communication
control
Other parameters related to the fieldbus configuration:
58.14 Communication
loss action
58.15 Communication
loss mode
58.16 Communication
loss time
EN
Warnings and faults
DE
Warning
Fault
ES
A2A1
2281
FR
-
2310
IT
A2B3
2330
TR
A2B4
2340
-
3130
-
3181
A3A1
3210
A3A2
3220
-
3381
-
5090
A5A0
5091
A7CE
6681
A7C1
7510
A7AB
-
AFF6
-
-
FA81
-
FA82
Setting
Description
Refresh settings
Validates any changed EFB configuration settings. Use
this after changing any parameters in group 58.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
Aux. code
Description
Current calibration
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
Overcurrent
The output current is more than the internal limit. This can
also be caused by an earth fault or phase loss.
Earth leakage
A load unbalance that is typically caused by an earth fault in
the motor or the motor cable.
Short circuit
There is a short-circuit in the motor or the motor cable.
Input phase loss
The intermediate DC circuit voltage oscillates due to missing
input power line phase.
Wiring or earth fault
Incorrect input and motor cable connection.
DC link overvoltage
Intermediate DC circuit voltage is too high.
DC link under-
Intermediate DC circuit voltage is too low.
voltage
Output phase loss
All three phases are not connected to the motor.
STO hardware fail-
STO hardware diagnostics has detected hardware failure.
ure
Contact ABB.
Safe torque off
The Safe torque off (STO) function is active.
EFB comm loss
Break in embedded fieldbus communication.
FBA A communica-
Communication lost between drive (or PLC) and fieldbus ad-
tion
apter.
Extension I/O con-
The I/O extension module types and locations specified by
figuration failure
parameters do not match the detected configuration.
Identification run
The motor ID run occurs at the next start.
Safe torque off 1
The Safe torque off circuit 1 is broken.
loss
Safe torque off 2
The Safe torque off circuit 2 is broken.
loss
58.28 EFB act1 type
58.34 Word order
58.31 EFB act1 transpar-
58.101 Data I/O 1
ent source
...
58.124 Data I/O 24 time
58.33 Addressing mode

Publicidad

loading