Descargar Imprimir esta página

EAS ELECTRIC EFMV2 Serie Manual De Instrucciones página 59

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

8. Remove the side board and the grille.
Hanging
screw bolt
9. Mount the indoor unit onto the
hanging screw bolts with a block.
Position the indoor unit on a flat level
by using a level to prevent leaks.
Shockproof cushion
Washer
Hanging screw bolt
NOTE: Confirm the minimum drain tilt is
1/100 or more.
Ceiling Installation
D. Refrigerant pipe
connection
(D.gas side)
E. Refrigerant
pipe connection
(E. Liquid side)
Drain point
Downward slope between(1-2)/100
Hanging arm
Side board
Screw nut
Overhang part
How to install the conduit installation
plate (if supplied)
1. Fix the sheath connector (not supply)
on the wire hole of the conduit
installation plate.
2. Fix the the conduit installation plate
on the chassis of the unit.
Chassis
Cord conduit
Conduit
installation plate
Wall-Mounted Installation
How to install the conduit installation
plate (if supplied)
1. Fix the sheath connector (not supply)
on the wire hole of the conduit
installation plate.
2. Fix the conduit installation plate on
the electric control box.
Electric control box
Conduit
installation
plate
22
The conduit
installation
plate
screws
(not supply)
screws
(not
supply)
V.1

Publicidad

loading