Room Controller
Network Address Switch Detail
After networking each panel an address will have to be assigned to each using the network address DIP Switch. The example
below describes its use to address the room controller. Each switch position (1–8) has a value associated with it (1–128).
Addresses 1 through 254 are valid for use but 255 (all values added together) is reserved for system use and should not be
used.
1.
Add the value for each switch position that is On to obtain the panel address.
Switch
Position
Value
1
+
2.
Issue a soft reset by pressing the reset button to assign the address to the panel.
Network Node
Address DIP Switch
www.cooperlighting.com
4
=
5 (Panel Address)
RS-485 Connection
Terminating Jumper
Communication
Status LEDs
Reset Button
ON
OFF
Greengate
9850-000362-06 page 18
October 2022