Power dedicated to domestic water production

MAX
value
In those units that can produce domestic water, once this function has been activated it is possible to
100 %
decide the percentage of power to use for the production. This function allows you to set a threshold to
guarantee reduced energy consumption during domestic water production.

Standby time in Input/Output

MAX
value
This parameter allows you to establish the standby time (in seconds) for reversing the 3-way valve
600 s
inserted in the system for producing domestic water.
Standby time in Input/Output
MAX
value
This parameter enables the possibility to join the ID digital clamp (marked on the electric card enclosed
with the unit as TRA) with a room thermostat on which the functioning of the compressors and supple-
mentary electric heaters will be disabled.
Remember also that setting this parameter with a value of:
• 1 or 2, you ENABLE this function
• 0 or 3, you DISABLE this function
0
3
Remember that the OPEN status of the clamp means:
• the function blocks the compressors and electric heaters if the parameter is set at 1
• the function blocks the compressors, pump and electric heaters if the parameter is set at 2
• the pump alarm (as in the previous software version), if the parameter is set at 3
Remember also that by setting this parameter at 3, the moducontrol card is compatible with the previ-
ous software version (3.6).

Enabling flow switch bypass

MAX
value
In those units that produce domestic water, the flow switch alarm can be bypassed to allow the correct
0
1
synchronisation between a diverting valve installed in the system, and unit functioning during the pro-
duction of hot domestic water.

Time for flow switch bypass

MAX
value
This parameter allows you to establish the time (in seconds) for flow switch bypass.
300 s
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameters only visible in the models with DCP installed
Parameters only visible in bicompressor models
Parameters only visible in the models with inverter compressor