Managing The Electric Heater; Selection Logic For Electric Heater Management Mode; Supplementary Electric Heater Logic; Replacement Electric Heater Logic - AERMEC MODUCONTROL Manual De Instrucciones

Regulación eléctrica
Ocultar thumbs Ver también para MODUCONTROL:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

The units with moducontrol offer the
possibility to manage an electric he-
ater; this heater can be managed in
different ways:
• supplementary (the simultaneous
use of the heat pump and the electric
heater);
• anti-freeze, or replacement (the heat
pump compressor is switched off and
the electric heater alone is activated);
The operational specifi cations of both
modes are shown in the diagrams be-
low.
The choice of supplementary or re-
placement mode depends on the
external air temperature, and in case
this falls below the threshold indica-
ted in the relative diagram.
WARNING: all parameters referred
to in the chart alongside are con-
tained in the electric heater menu,
shown on the next pages.

Managing the electric heater

Selection logic for electric heater management mode

Electric heater
REPLACEMENT mode

Supplementary electric heater logic:

ON
Compressor
ON
Electric heater

Replacement electric heater logic:

Replacement electric heater logic:
Compressor
OFF
ON
Electric heater
Electric heater
SUPPLEMENTARY mode
Parameter tA2
Parameter tA1
(Index 5)
(Index 4)
Parameter Bri
Parameter Sri
(Index 3)
Parameter Bri
(Index 3)
IMDCFJ. 12.05 6343841_03
Fig.11
Electric heater
always switched off
External air
temperature
Fig.12
HEATING setpoints
(Index 2)
External air
of system water
OFF
Fig.13
HEATING setpoints
External air
of system water
OFF
EN
65